Table 13 Additional Cooler Weights*
COOLER
FRAME
WATERBOX
TYPE
NUMBER
OF PASSES
DESIGN MAXIMUM
WATER PRESSURE
ADDITIONAL
DRY WEIGHT
ADDITIONAL
WATER WEIGHT
psig kPa lb kg lb gal kg L
3
NIH 1, 3 150 1034 655 297
NIH 1, 3 300 2068 2226 1010
NIH 2 300 2068 1406 638
Marine 1, 3 150 1034 780 354 3192 383 1448 1 448
Marine 2 150 1034 390 177 1596 191 724 724
Marine 1, 3 300 2068 3412 1548 3192 383 1448 1 448
Marine 2 300 2068 1706 774 1596 191 724 724
4
NIH 1, 3 150 1034 515 234
NIH 1, 3 300 2068 2941 1334
NIH 2 300 2068 2085 946
Marine 1, 3 150 1034 2100 953 5102 612 2314 2 314
Marine 2 150 1034 792 359 2551 306 1157 1 157
Marine 1, 3 300 2068 3844 1744 5102 612 2314 2 314
Marine 2 300 2068 2536 1150 2551 306 1157 1 157
NIH Nozzle-In-Head
*When using a machine configuration other than 2-pass, NIH water-
boxes with 150 psig (1038 kPa) covers, add the weights listed in this
table to the appropriate weights in Table 10 to obtain the correct cooler
weight.
Table 14 Marine Waterbox Cover Weights*
HEAT EXCHANGER
SIZE
DESIGN MAXIMUM WATER PRESSURE COOLER CONDENSER
psi kPa lb kg lb kg
31-33
150 1034 1667 756 1092 495
300 2068 2280 1034 1436 651
41-48
150 1034 2236 1015 1275 579
300 2068 3060 1389 1660 754
51-57
150 1034 1643 746
300 2068 2243 1018
*Heat exchangers with marine waterboxes have heavier dry and operating weights than heat exchangers with nozzle-
in-head waterboxes.
100