Table 8 LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides (cont)
G. COMPRESSOR JUMPSTART AND REFRIGERANT PROTECTION
PRIMARY MESSAGE SECONDARY MESSAGE ALARM MESSAGE/PRIMARY CAUSE ADDITIONAL CAUSE/REMEDY
UNAUTHORIZED
OPERATION
UNIT SHOULD BE
STOPPED
CA P Emergency: Compressor
running without control authorization.
Compressor is running with more than 10% RLA
and control is trying to shut it down. Throw power
off to compressor if unable to stop. Determine cause
before repowering.
POTENTIAL FREEZE-UP EVAP PRESS/TEMP
TOO LOW
ERT Emergency: Freeze-up
prevention.
Determine cause. If pumping refrigerant out of ma-
chine, stop operation and go over pumpout
procedures.
FAILURE TO STOP DISCONNECT POWER RUN AUX Emergency: DISCONNECT
POWER.
Starter and run and start contacts are energized
while control tried to shut down. Disconnect power
to starter.
LOSS OF
COMMUNCIATION
WITH STARTER Loss of Communication with Starter: Check
machine.
Check wiring from PSIO to SMM. Check SMM mod-
ule troubleshooting procedures.
STARTER CONTACT
FAULT
ABNORMAL 1CR OR
RUN AUX
1CR AUX Starter Contact Fault: Check
1CR/1M aux. contacts.
Starter run and start contacts energized while ma-
chine was off. Disconnect power.
POTENTIAL FREEZE UP COND PRESS/TEMP
TOO LOW
CRT [VALUE] exceeded limit of [LIMIT]*
Emergency: Freeze-up prevention.
The condenser pressure transducer is reading a
pressure that could freeze the water in the con-
denser tubes. Check for condenser refrigerant leaks,
bad transducers, or transferred refrigerant. Place
the unit in Pumpdown mode to eliminate ALARM
if vessel is evacuated.
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or alarm condition. [VALUE]
is the actual pressure, temperature, voltage, etc., at which the control tripped.
H. NORMAL RUN WITH RESET, TEMPERATURE, OR DEMAND
PRIMARY MESSAGE SECONDARY MESSAGE PROBABLE CAUSE/REMEDY
RUNNING RESET ACTIVE 4-20MA SIGNAL
Reset program active based upon Config table setup.RUNNING RESET ACTIVE REMOTE SENSOR CONTROL
RUNNING RESET ACTIVE CHW TEMP DIFFERENCE
RUNNING TEMP CONTROL LEAVING CHILLED WATER Default method of temperature control.
RUNNING TEMP CONTROL ENTERING CHILLED WATER ECW control activated on Config table.
RUNNING TEMP CONTROL TEMPERATURE RAMP LOADING Ramp loading in effect. Use Service1 table to modify.
RUNNING DEMAND LIMITED BY DEMAND RAMP LOADING Ramp loading in effect. Use Service1 table to modify.
RUNNING DEMAND LIMITED BY LOCAL DEMAND SETPOINT Demand limit setpoint is , actual demand.
RUNNING DEMAND LIMITED BY 4-20MA SIGNAL
Demand limit is active based on Config table setup.RUNNING DEMAND LIMITED BY CCN SIGNAL
RUNNING DEMAND LIMITED BY LOADSHED/REDLINE
RUNNING TEMP CONTROL HOT GAS BYPASS
Hot Gas Bypass is energized. See surge prevention in the control
section.
RUNNING DEMAND LIMITED BY LOCAL SIGNAL Active demand limit manually overridden or Status01 table.
RUNNING TEMP CONTROL ICE BUILD MODE Machine is running under Ice Build temperature control.