EasyManua.ls Logo

Carrier 17DA - Pre-Start up Check List

Carrier 17DA
32 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53170002-01 Printed in U.S.A. Form 17DA-3SS Pg CL-1 3-09 Replaces: 17DA-2SS,
17DA-3SO
Copyright 2009 Carrier Corporation
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
PRE-START UP CHECK LIST
1. Steam System
a. Is steam available? ______
b. Have the steam lines been blown out and checked for cleanliness? ______
c. Have the turbine steam inlet and exhaust chambers been checked for foreign material before steam lines are attached? ______
d. Are there adequate pipe hangers and supports on the steam lines and has an analysis of the piping been concluded to eliminate
piping stress on the turbine? ______
e. Have limiting rods been placed on expansion joints when they are used? ______
f. If a trip and throttle valve is supplied, does it have adequate support under it so that no weight or stress is placed
on the turbine? ______
g. Have all steam leak-off lines and drains been piped as indicated on the Dresser-Rand Outline drawing? ______
h. Has an atmospheric relief valve been installed in the exhaust line between the turbine and the first block valve? ______
2. Turbine Preparation
a. Has the turbine been rough aligned to the driven machine and grouted in? ______
b. Have all shipping plugs and/or blind flanges been removed from the oil pipes and lube console and oil lines cleaned
prior to installing? ______
c. Has oil tank been cleaned and inspected in preparation to filling with oil? ______
d. When oil console is supplied by others, has provisions been made to circulate oil and checked for cleanliness without
passing oil through the turbine? ______
e. Is piping complete and water available for oil cooler? ______
f. Has proper oil for turbine and driven machine been obtained and brought to jobsite? ______
g. Has auxiliary oil pump, where supplied, been checked for correct rotation? ______
h. Are pneumatic and electrical connections to the turbine governor and safety devices completed? ______
i. Is piping and wiring to gauge board, where furnished, complete? ______
3. Condensing Turbines Only
a. Has a means been provided to drain the casing while under vacuum? ______
b. Have the condenser condensate pumps been checked for correct rotation? ______
c. Has the condenser hot well level control been checked for correct operation? ______
Signed By: ____________________________________ Date: ____________