18
Table 12 — 19XR Two-Stage Compressor Frame Size 7
Heat Exchanger Weights (English) (cont)
*Rigging weights are for standard tubes of standard wall thickness (0.025-in. [0.635 mm]
wall) and do not include refrigerant weight.
†See Model Number Nomenclature on page 5.
NOTES:
1. Cooler weight includes the suction elbow and the distribution piping to the economizer
and two-pass Victaulic dished heads.
2. Condenser weight includes the high side float chamber, discharge pipe, and
the distri-
bution piping weight from the economizer to the float chamber and two-pass Victaulic
dished heads.
CODE†
DRY RIGGING WEIGHT (lb)* REFRIGERANT WEIGHT (lb) WATER WEIGHT (lb)
COOLER ONLY CONDENSER ONLY COOLER ONLY CONDENSER ONLY COOLER ONLY CONDENSER ONLY
D60 — 38,296 — 2097 — 11,473
D61 — 39,624 — 2097 — 12,309
D62 — 41,031 — 2097 — 13,210
D65 — 37,624 — 2097 — 11,617
D66 — 38,837 — 2097 — 12,387
D67 — 40,460 — 2097 — 13,410
D80 — 41,916 — 2359 — 12,447
D81 — 43,382 — 2359 — 13,388
D82 — 44,963 — 2359 — 14,401
D85 — 42,058 — 2359 — 12,609
D86 — 43,408 — 2359 — 13,475
D87 — 45,204 — 2359 — 14,626
D6A — 35,286 — 1947 — 11,401
D6B — 36,328 — 1947 — 12,255
D6C — 37,288 — 1947 — 13,078
D6F — 34,447 — 1947 — 11,448
D6G — 35,637 — 1947 — 12,408
D6H — 36,663 — 1947 — 13,278
D8A — 38,494 — 2190 — 12,366
D8B — 39,633 — 2190 — 13,327
D8C — 40,731 — 2190 — 14,253
D8F — 38,479 — 2190 — 12,419
D8G — 39,761 — 2190 — 13,499
D8H — 40,922 — 2190 — 14,478