CONNECT CONTROL OUTPUTS — Connect auxiliary
equipment, chilled and condenser water pumps, and spare
alarms as required and indicated on job wiring drawings.
CONNECT STARTER The 19XR two-stage chiller is
available with a free-standing, field-installed starter or VFD
(Fig. 26).
Assemble and install compressor terminal box in desired
orientation, and cut necessary conduit openings in conduit sup-
port plates. See Fig. 26 and 27. Attach power leads to
compressor terminals in accordance with job wiring drawings,
observing caution label in terminal box. Use only copper con-
ductors. The motor must be grounded in accordance with NEC,
applicable local codes, and job wiring diagrams. Installer is re-
sponsible for any damage caused by improper wiring between
starter and compressor motor. See Fig. 28-34 for VFD (vari-
able frequency drive), control, IOB (input/output board), and
ISM (integrated starter module) starter wiring diagrams.
IMPORTANT: Be sure to ground the power circuit in accor-
dance with the National Electrical Code (NEC), applicable
local codes, and job wiring diagrams. Also, make sure cor-
rect phasing is observed for proper rotation.
IMPORTANT: Do not insulate terminals until wiring
arrangement has been checked and approved by Carrier
start-up personnel. Also, make sure correct phasing is fol-
lowed for proper motor rotation.
STARTER
15
Fig. 26 — 19XR Chiller with Free-Standing Starter
a19-2069
LEGEND
1—Disconnect
2—Free-standing Compressor Motor Starter
3—Compressor Motor Terminal Box
4—Power Panel
5—Control Panel
6—Vents
7—Pressure Gages
8—Chilled Water Pump
9—Condenser Water Pump
10 Chilled Water Pump Starter
11 Condensing Water Pump Starter
12 Cooling Tower Fan Starter
(Low Fan, High Fan)
13 Disconnect
14 Oil Pump Disconnect (See Note 4)
15 Strainer
Piping
Control Wiring
Power Wiring
NOTES:
1. Wiring and piping shown are for general point-of-connection only and are not
intended to show details for a specific installation. Certified field wiring and
dimensional diagrams are available on request.
2. All wiring must comply with applicable codes.
3. Wiring not shown for optional devices such as:
• Remote Start/Stop
• Remote Alarms
• Optional Safety Device
• 4 to 20 mA Resets
• Optional Remote Sensors
4. Oil pump disconnect may be located within the enclosure of Item 2 —
Free-standing Compressor Motor Starter.
5. IMPORTANT: Carrier suggests that a structural engineer be consulted if trans-
mission of vibrations from mechanical equipment is of concern.
6. Isolation valves are recommended on the cooler and condenser piping to each
chiller for service.
7. Operating environment — Chiller should be installed in an indoor environment
where the ambient temperature is 40 to 104 F (4 to 40 C) with a relative humid-
ity (non-condensing) of 95% or less. To ensure that electrical components
operate properly, do not locate the chiller in an area exposed to dust, dirt, cor-
rosive fumes, or excessive heat and humidity.