Loading...
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53190039-01 Printed in U.S.A. Form 19XR-CLT-15SI Pg CL-2 10-16 Replaces: 19XR-CLT-14SI
© Carrier Corporation 2016
-
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -- - - - - - - - - - - - - - - - - - - -
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
7. The machine’s starter wiring is complete. The wiring is
installed per installation instructions and certified prints.
a. Power wiring to compressor motor. (Motor leads will
not be taped until the Carrier technician Megger tests
the motor.)
b. 3-phase power wiring to control box
c. Carrier controls can independently energize water
pumps and tower fan.
d. Line side voltage is within ±10% of chiller nameplate
voltage.
e. Other
8. The motor starter has not been supplied by Carrier. It
has been installed according to the manufacturer’s
instructions.
9. Inspect installation location. Does the starter/controls/VFD
enclosure protection rating match the installation site
environment?
NOTE: NEMA Type 1 enclosures are constructed for indoor use to provide a degree of protection to personnel against
incidental contact with the enclosed equipment and to provide a degree of protection against falling dirt. This type of
enclosure does not protect against water, dust, moisture, or airborne contaminants.
COMMENTS: