CL-3
19XRV PIC III SETPOINT TABLE CONFIGURATION SHEET
Upload all control configuration tables via service tool? Ye s
No
ICVC Software Part Number (See ICVC Configuration Screen):
ICVC Controller Identification (See ICVC Configuration Screen):BUS: ADDRESS:
VFD Gateway Version Number (See VFD_STAT Screen):
VFD Inverter Version Number (See VFD_STAT Screen):
VFD Rectifier Version Number (See VFD_STAT Screen):
DESCRIPTION RANGE UNITS DEFAULT VALUE
Base Demand Limit 40 to 100 % 100
LCW Setpoint
10 to 120
(-12.2 to 48.9)
DEG F (C) 50.0 (10)
ECW Setpoint
15 to 120
(-9.4 to 48.9)
DEG F (C) 60.0 (15.6)
Ice Build Setpoint
15 to 60
(-9.4 to 15.6)
DEG F (C) 40.0 (4.4)
Tower Fan High Setpoint
55 to 105
(13 to 41)
DEG F (C) 75 (24)