Table 3 — CVC Display Data (cont)
EXAMPLE 14 — NET_OPT DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight
.
NOTE: No variables are available for CCN read or write operation.
EXAMPLE 15 — ISM_CONF DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight
.
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION STATUS UNITS POINT DEFAULT
Loadshed Function
Group Number 1-16
ldsgrp 0
Demand Limit Decrease
0-06 % ldsdelta 20
Maximum Loadshed Time
30-480 MIN maxldstm 60
CCN Occupancy Config:
Schedule Number
3-99 occpcxxe 3
Broadcast Option
0-1 DSABLE/ENABLE occbrcst DSABLE
Alarm Configuration
Re-Alarm Time
0-1440 MIN 30
Alarm Routing
00000000-11111111 10000000
DESCRIPTION STATUS UNITS POINT DEFAULT
Starter Type
0-2 starter 1
(0 = Full, 1 = Red, 2 = SS/VFD)
Motor Rated Line Voltage
200-13200 VOLTS v_fs 460
Volt Transformer Ratio:1
1-33 vt_rat 1
Overvoltage Threshold
105-115 % overvolt 115
Undervoltage Threshold
85-95 % undvolt 85
Over/Under Volt Time
1-10 SEC uvuntime 5
Voltage % Imbalance
1-10 % v_unbal 10
Voltage Imbalance Time
1-10 SEC v_time 5
Motor Rated Load Amps
10-5000 AMPS a_fs 200
Motor Locked Rotor Trip
100-60000 AMPS motor_r 1000
Locked Rotor Start Delay
1-10 cycles lrdelay 5
Starter LRA Rating
100-60000 AMPS star_lr 2000
Motor Current CT Ratio:
13-1000 ct_turns 100
Current % Imbalance
5-40 % c_unbal 15
Current Imbalance Time
1-10 SEC c_time 5
3 Grnd Fault CT’s? (1 = No)
0-1 NO/YES gf_phase YES
Ground Fault CT Ratio:1
150 gf_ctr 150
Ground Fault Current
1-25 AMPS gf_amps 15
Ground Fault Start Delay
1-20 cycles gf_delay 10
Ground Fault Persistence
1-10 cycles gf_pers 5
Single Cycle Dropout
0/1 DSABLE/ENABLE cycdrop DSABLE
Frequency = 60 Hz? (No = 50)
0/1 NO/YES freq YES
Line Frequency Faulting
0/1 DSABLE/ENABLE freq_en DSABLE
MENU
SERVICE
EQUIPMENT CONFIGURATION
SELECT
NET_OPT
MENU
SERVICE
ISM (STARTER) CONFIG DATA
SELECT
ISM_CONF