34
Table 3 — CVC Display Data (cont)
EXAMPLE 16 — OPTIONS DISPLAY SCREEN
To access this display from the
CVC default
screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight
.
NOTE: No variables are available for CCN read or write operation.
DESCRIPTION STATUS UNITS POINT DEFAULT
Auto Restart Option
0/1 DSABLE/ENABLE astart DSABLE
Remote Contacts Open
0/1 DSABLE/ENABLE r_contact DSABLE
Soft Stop Amps Threshold
40-100 % softstop 100
Stall/Hot Gas Bypass
Stall Limit/HGBP Option
0/1 stall_hgbp 0
Select: Stall=0, HGBP=1
Min. Load Point (T1/P1)
Stall/HGBP Delta T1
0.5-20 ^F hgb_dt1 1.5
Stall/HGBP Delta P1
30-170 PSI hgb_dp1 150
Full Load Point (T2/P2)
Stall/HGBP Delta T2
0.5-20 ^F hbg-dt2 4
Stall/HGBP Delta P2
30-250 PSI hgb_dp2 200
Stall/HGBP Deadband
0.5-3 ^F hbg_db 1
Stall Protection
Stall Delta % Amps
5-20 % stall_a 10
Stall Time Period
7-10 MIN stall_t 8
Ice Build Control
Ice Build Option
0-1 DSABLE/ENABLE ibopt DSABLE
Ice Build Termination
0-2 ibterm 0
0=Temp, 1=Contacts, 2=Both
Ice Build Recycle
0/1 DSABLE/ENABLE ibrecyc DSABLE
Refrigerant Leak Option
0/1 DSABLE/ENABLE REF_OPT DSABLE
Refrigerant Leak Alarm
4-20 mA REF_LEAK 20
Head Pressure Reference
Delta P @ 0% (4mA)
20-30 PSI HPDP0 25
Delta P @ 100% (20mA)
35-50 PSI HPDP100 35
Minimum Output
0-100 % HPDPMIN% 0
MENU
SERVICE
EQUIPMENT SERVICE
SELECT
OPTIONS