80
Table 9 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
D. PRE-START ALERTS: These alerts only delay start-up. When alert is corrected, the start-up will continue.
No reset is necessary.
*[LIMIT] is shown on the CVC as temperature, pressure, voltage, etc., predefined or selected by the operator as an override or an alert. [VALUE] is
the actual pressure, temperature, voltage, etc., at which the control tripped.
E. START-UP IN PROGRESS
STATE
PRIMARY
MESSAGE
SECONDARY
MESSAGE
ALARM MESSAGE
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
100
PRESTART
ALERT
STARTS LIMIT
EXCEEDED
100->Excessive compressor
starts (8 in 12 hours)
Depress the RESET softkey if additional start is
required. Reassess start-up requirements.
102
PRESTART
ALERT
HIGH MOTOR
TEMPERATURE
102->Comp Motor Winding
Temp [VALUE] exceeded limit
of [LIMIT]*.
Check motor sensors for wiring and accuracy.
Check motor cooling line for proper operation, or
restrictions.
Check for excessive starts within a short time
span.Check configurable range in SETUP1 screen.
103
PRESTART
ALERT
HIGH DISCHARGE
TEMP
103->Comp Discharge Temp
[VALUE] exceeded limit of
[LIMIT]*.
Allow discharge sensor to cool.
Check for sensor wiring and accuracy.
Check for excessive starts.
Check configurable range in SETUP1 screen.
104
PRESTART
ALERT
LOW REFRIGERANT
TEMP
104->Evaporator Refrig Temp
[VALUE] exceeded limit of
[LIMIT]*.
Check transducer wiring and accuracy.
Check for low chilled fluid supply temperatures.
Check refrigerant charge.
105
PRESTAR
ALERT
LOW OIL
TEMPERATURE
105->Oil Sump Temp [VALUE]
exceeded limit of [LIMIT]*.
Check oil heater contactor/relay and power.
Check oil level and oil pump operation.
106
PRESTART
ALERT
HIGH CONDENSER
PRESSURE
106->Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
Check transducer wiring and accuracy.
Check for high condenser water temperatures.
107
PRESTART
ALERT
LOW LINE
VOLTAGE
107->Average Line Voltage
[VALUE] exceeded limit of
[LIMIT]*.
Check voltage supply. Check voltage transformers.
Consult power utility if voltage is low.
108
PRESTART
ALERT
HIGH LINE
VOLTAGE
108->Average Line Voltage
[VALUE] exceeded limit of
[LIMIT]*.
Check voltage supply.
Check power transformers.
Consult power utility if voltage is high.
PRIMARY MESSAGE
SECONDARY MESSAGE CAUSE/REMEDY
STARTUP IN PROGRESS
OCCUPIED MODE Chiller is starting. Time schedule is occupied.
STARTUP IN PROGRESS
REMOTE CONTACT CLOSED Chiller is starting. Remote contacts are enabled and closed.
STARTUP IN PROGRESS
START COMMAND IN EFFECT Chiller is starting. Chiller START/STOP in MAINSTAT manually
forced to start.
AUTORESTART IN PROGRESS
OCCUPIED MODE Chiller is starting after power failure. Time schedule is occupied.
AUTORESTART IN PROGRESS
REMOTE CONTACT CLOSED Chiller is starting after power failure. Remote contacts are enabled
and closed.
AUTORESTART IN PROGRESS
START COMMAND IN EFFECT Chiller is starting after power failure. Chiller START/STOP on
MAINSTAT manually forced to start.