Table 9 — CVC Primary and Secondary Messages and
Custom Alarm/Alert Messages with Troubleshooting Guides (cont)
F. NORMAL RUN
G. NORMAL RUN WITH OVERRIDES
*[LIMIT] is shown on the CVC as the temperature, pressure, voltage, etc., set point predefined or selected by the operator as an override, alert, or
alarm condition. [VALUE] is the actual pressure, temperature, voltage, etc., at which the control has recorded at the time of the fault condition.
H. OUT-OF-RANGE SENSOR ALARMS
PRIMARY MESSAGE
SECONDARY MESSAGE CAUSE/REMEDY
RUNNING — RESET ACTIVE
4-20 mA SIGNAL Auto chilled water reset active based on external input.
RUNNING — RESET ACTIVE
REMOTE TEMP SENSOR Auto chilled water reset active based on external input.
RUNNING — RESET ACTIVE
CHW TEMP DIFFERENCE Auto chilled water reset active based on cooler
∆
T.
RUNNING — TEMP CONTROL
LEAVING CHILLED WATER Default method of temperature control.
RUNNING — TEMP CONTROL
ENTERING CHILLED WATER Entering Chilled Water (ECW) control enabled in TEMP_CTL screen
RUNNING — TEMP CONTROL
TEMPERATURE RAMP LOADING Ramp Loading in effect. Use RAMP_DEM screen to modify.
RUNNING — DEMAND LIMITED
BY DEMAND RAMP LOADING Ramp Loading in effect. Use RAMP_DEM screen to modify.
RUNNING — DEMAND LIMITED
BY LOCAL DEMAND SETPOINT Demand limit set point is less than actual demand.
RUNNING — DEMAND LIMITED
BY 4-20 mA SIGNAL Demand limit is active based on external auto demand limit option.
RUNNING — DEMAND LIMITED
BY CCN SIGNAL Demand limit is active based on control limit signal from CCN.
RUNNING — DEMAND LIMITED
BY LOADSHED/REDLINE Demand limit is active based on LOADSHED screen set-up.
RUNNING — TEMP CONTROL
HOT GAS BYPASS Hot gas bypass option is energized. See stall prevention in the control
section.
RUNNING — DEMAND LIMITED
BY LOCAL SIGNAL Active demand limit manually overridden on MAINSTAT table.
RUNNING —TEMP CONTROL
ICE BUILD MODE Chiller is running under Ice Build temperature control.
STATE
PRIMARY
MESSAGE
SECONDARY
MESSAGE
ALARM MESSAGE
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
120
RUN CAPACITY
LIMITED
HIGH CONDENSER
PRESSURE
120->Condenser Pressure
[VALUE] exceeded limit of
[LIMIT]*.
Check for high condenser water temperatures.
Check setting in SETUP1.
121
RUN CAPACITY
LIMITED
HIGH MOTOR
TEMPERATURE
121->Comp Motor Winding
Temp [VALUE] exceeded limit
of [LIMIT]*.
Check motor cooling lines.
Check for closed valves.
Check setting in SETUP1.
122
RUN CAPACITY
LIMITED
LOW EVAP
REFRIG TEMP
122->Evaporator Refrig
Temp [VALUE] exceeded limit
of [LIMIT]*.
Check refrigerant charge.
Check for low entering cooler temperatures.
123
RUN CAPACITY
LIMITED
HIGH COMPRESSOR
LIFT
123->Stall Prevention
Override: Lift Too High For
Compressor.
Check for high condenser water temperatures
or low suction temperature.
124
RUN CAPACITY
LIMITED
MANUAL SLIDE
VALVE
124->Run Capacity Limited:
Manual Slide Valve Control.
Slide valve point has been forced in MAINSTAT
screen. Release force to continue normal
operation.
125
RUN CAPACITY
LIMITED
LOW DISCHARGE
SUPERHEAT
No messages. Check oil charge.
Check refrigerant charge.
126
RUN CAPACITY
OVERRIDE
ROTOR INLET
TEMPERATURE
126->Run Capacity Override:
Rotor Inlet Temp.
STATE
PRIMARY
MESSAGE
SECONDARY
MESSAGE
ALARM MESSAGE
PRIMARY CAUSE
ADDITIONAL CAUSE/REMEDY
260
SENSOR
FAULT
LEAVING CHILLED
WATER
260->Sensor Fault:
Leaving Chilled Water
Check sensor resistance or voltage drop.
Check for proper wiring.
261
SENSOR
FAULT
ENTERING CHILLED
WATER
261->Sensor Fault:
Entering Chilled Water
Check sensor resistance or voltage drop.
Check for proper wiring.
262
SENSOR
FAULT
CONDENSER
PRESSURE
262->Sensor Fault:
Condenser Pressure
Check sensor wiring.
263
SENSOR
FAULT
EVAPORATOR
PRESSURE
263->Sensor Fault:
Evaporator Pressure
Check sensor wiring.
264
SENSOR
FAULT
ROTOR INLET
TEMP
264->Sensor Fault:
Rotor Inlet Temp
Check sensor resistance or voltage drop.
Check for proper wiring.
265
SENSOR
FAULT
COMPRESSOR
MOTOR TEMP
265->Sensor Fault:
Comp Motor Winding Temp
Check sensor resistance or voltage drop.
Check for proper wiring.
266
SENSOR
FAULT
OIL SUMP
TEMP
266->Sensor Fault:
Oil Sump Temp
Check sensor resistance or voltage drop.
Check for proper wiring.
267
SENSOR
FAULT
COMP OIL
PRESS DIFF
267->Sensor Fault:
Oil Sump Temp
Check sensor resistance or voltage drop.
Check for proper wiring.
268
SENSOR
FAULT
CHILLED WATER
FLOW
269->Sensor Fault:
Chilled Water Delta P
Check sensor wiring and accuracy.
269
SENSOR
FAULT
COND WATER
FLOW
270->Sensor Fault:
Cond Water Delta P
Check sensor wiring and accuracy.