DETAILED COOLING CAPACITIES
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES deg F
75 85 95 105 115 125
CFM EWB
Capacity
MBtuh†
To t a l
System
KW**
Capacity
MBtuh†
To t a l
System
KW**
Capacity
MBtuh†
To t a l
System
KW**
Capacity
MBtuh†
To t a l
System
KW**
Capacity
MBtuh†
To t a l
System
KW**
Capacity
MBtuh†
To t a l
System
KW**
To t a l Sens‡ To t al Sens‡ To tal Sens‡ To t a l Sens‡ To t al Sens‡ To tal Sens‡
24ABA460A30 Outdoor Section With CAP**6024A** Indoor Section
1750
72 70.52 37.08 3.97 67.20 35.81 4.38 63.70 34.48 4.83 59.99 33.10 5.32 55.97 31.62 5.86 51.51 30.01 6.45
67 64.33 45.47 3.92 61.31 44.20 4.33 58.13 42.87 4.78 54.75 41.49 5.27 51.12 40.02 5.82 47.11 38.42 6.40
62 58.81 53.84 3.87 56.12 52.55 4.28 53.31 51.19 4.73 50.40 49.71 5.23 47.55 47.55 5.78 44.50 44.50 6.38
57 57.17 57.17 3.86 55.01 55.01 4.27 52.72 52.72 4.73 50.25 50.25 5.23 47.55 47.55 5.78 44.50 44.50 6.38
2000
72 71.76 38.86 4.07 68.29 37.57 4.48 64.63 36.22 4.93 60.76 34.81 5.43 56.59 33.31 5.96 51.97 31.67 6.55
67 65.49 48.34 4.02 62.33 47.04 4.43 59.00 45.69 4.88 55.50 44.28 5.37 51.73 42.78 5.92 47.58 41.13 6.50
62 60.13 57.72 3.98 57.39 56.32 4.38 54.66 54.66 4.84 52.02 52.02 5.34 49.12 49.12 5.89 45.84 45.84 6.48
57 59.48 59.48 3.97 57.15 57.15 4.38 54.68 54.68 4.84 52.03 52.03 5.34 49.12 49.12 5.89 45.85 45.85 6.48
2250
72 72.67 40.54 4.17 69.08 39.23 4.58 65.29 37.86 5.03 61.30 36.43 5.52 57.00 34.90 6.06 52.25 33.24 6.64
67 66.34 51.06 4.12 63.07 49.75 4.53 59.64 48.38 4.98 56.04 46.94 5.47 52.17 45.40 6.01 47.92 43.68 6.60
62 61.32 61.32 4.08 58.90 58.90 4.49 56.27 56.27 4.95 53.45 53.45 5.45 50.38 50.38 6.00 46.91 46.91 6.59
57 61.37 61.37 4.08 58.90 58.90 4.49 56.27 56.27 4.95 53.46 53.46 5.45 50.38 50.38 6.00 46.92 46.92 6.59
Multipliers for determining the performance with other indoor sections.
Cooling
Indoor Model
Capacity Power Furnace Model
*CAP**6024A** 1.00 1.00
CAP**6021A** 0.98 0.98
CNPH*6024A** 0.99 0.99
CNPV*6024A** 0.99 0.99
CSPH*6012A* * 1.00 1.00
FV4BNB006 1.00 0.96
FX4CN(B,F)060 1.01 1.01
FY4ANB060 1.00 1.03
CNPH*6024A** 0.97 0.97 58CV(A,X)110---20
CSPH*6012A* * 0.98 0.98 58CV(A,X)110 ---20
CAP**6024A** 0.98 0.94 58CV(A,X)135---22
CNPH*6024A** 0.97 0.93 58CV(A,X)135---22
CNPV*6024A** 0.97 0.93 58CV(A,X)135---22
CSPH*6012A* * 0.98 0.94 58CV(A,X)135 ---22
CAP**6024A** 0.98 0.94 58CV(A,X)155---22
CNPH*6024A** 0.98 0.94 58CV(A,X)155---22
CNPV*6024A** 0.98 0.94 58CV(A,X)155---22
CSPH*6012A* * 0.98 0.94 58CV(A,X)155 ---22
CAP**6021A** 0.93 0.93 58MVB080---20
CNPH*6024A** 0.94 0.94 58MVB080---20
CSPH*6012A* * 0.95 0.95 58MVB080---20
CNPH*6024A** 0.94 0.90 58MVB100---20
CSPH*6012A* * 0.95 0.91 58MVB100---20
CNPH*6024A** 0.94 0.90 58MVB120---20
CNPV*6024A** 0.94 0.90 58MVB120---20
CSPH*6012A* * 0.95 0.91 58MVB120---20
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable
practice.
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240--94. If additional
tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
{ Total a nd sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F (27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C),
deduct 835 Btuh (245 kW) per 1000 CFM (480 L/S) of indoor coil a ir for each degree below 80_F(27_C),oradd835Btuh(245kW)
per 1000 CFM (480 L/S) of indoor coil air per degree above 80_F(27_C).
When the required data fall between the published data, interpolation may be performed.
** Total system kW is t otal of indoor and outdoor unit kilowatts.