7
ELECTRICAL DATA
U N I T S I Z E ---
VOLTAGE,
SERIES
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN WIRE
SIZE{
MIN WIRE SIZE{
MAX
LENGTH
(FT)}
MAX
LENGTH
(FT)}
MAX FUSE**
or
CKT BRK AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
18--- 30
208/230/1 253 197
40.3 7.7 0.5 10.1 14 14 78 74 15
24--- 31 54.0 10.4 0.75 13.8 14 14 57 54 20
30--- 31 68.0 14.1 1.1 18.7 14 14 42 40 30
36--- 31 77.0 14.4 1.1 19.1 12 12 65 62 30
42--- 30 104.0 19.2 1.4 25.4 10 10 79 75 40
48--- 31 137.0 20.2 1.2 26.4 10 10 76 72 40
60--- 32 141.0 25.3 1.2 32.9 8 8 94 90 50
60--- 33 150.0 22.4 1.2 29.2 8 8 94 90 50
30--- 51
208/230/3 253 197
58.0 9.9 1.1 13.5 14 14 67 64 20
36--- 51 88.0 10.0 1.4 13.9 14 14 65 62 20
42--- 50 88.0 12.8 1.4 17.4 12 12 83 79 25
48--- 51 83.1 13.1 1.2 17.6 12 12 82 78 25
60--- 52 104.0 15.8 1.2 21.0 10 10 110 104 30
60--- 53 123.0 17.3 1.2 22.8 10 10 101 96 35
36--- 61
460/3 506 414
38.0 5.8 0.7 7.9 14 14 230 219 15
42--- 60 44.0 6.0 0.7 8.2 14 14 222 211 15
48--- 61 41.0 6.1 0.6 8.2 14 14 222 211 15
60--- 62 52.0 7.3 0.6 9.7 14 14 187 178 15
60--- 63 55.0 8.4 0.6 11.1 14 14 164 156 15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30˚ C(86˚ F), consult table 310---16 of th e NEC (ANSI/NFPA 70). The a mpacity of non ---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60˚ C (140˚ F) conditions, per the NEC (ANSI/NFPA 70) Article 336 ---26. If other than uncoated (no---plated), 60
or 75˚ C (140 or 167˚ C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables
of the NEC (ANSI/NFPA 70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- F u l l L o a d Am p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
A--WEIGHTED SOUND LEVEL (DBA)
UNIT SIZE ---VOLTAGE,SERIES
STANDARD
RATI NG
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
18--- 30 76 53.0 61.5 66.5 69.0 67.0 62.5 56.5
24--- 31 76 53.0 61.5 68.5 69.0 66.0 63.5 60.5
30--- 31
30--- 51
76 51.0 63.0 67.0 69.0 67.0 65.5 62.0
36--- 31
36--- 51
36--- 61
76 53.5 65.0 69.5 70.0 68.5 65.5 61.0
42--- 30
42--- 50
42--- 60
79 60.5 68.5 71.5 75.5 69.5 65.5 66.0
48--- 31
48--- 51
48--- 61
80 51.5 63.5 66.0 76.0 68.0 66.5 63.5
60--- 32/33
60--- 52/53
60--- 62/63
80 53.0 62.5 67.0 72.5 67.5 67.5 66.0
A--WEIGHTED SOUND POWER (DBA) WI TH ACCESSORY SOUND HOOD
UNIT SIZE ---VOLTAGE,SERIES
STANDARD
RATI NG
TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)
125 250 500 1000 2000 4000 8000
18--- 30 73 53.5 62.0 67.5 69.0 67.0 62.0 56.0
24--- 31 74 53.5 61.5 68.5 68.5 66.0 62.5 57.0
30--- 31
30--- 51
73 53.5 62.5 67.0 68.5 66.0 62.5 58.0
36--- 31
36--- 51
36--- 61
76 53.5 65.0 69.5 70.0 68.5 65.5 61.0
42--- 30
42--- 50
42--- 60
78 61.5 68.0 71.5 74.5 68.5 63.0 61.5
48--- 31
48--- 51
48--- 61
79 53.0 63.5 65.0 75.0 66.0 62.0 59.5
60--- 32/33
60--- 52/53
60--- 62/63
76 53.5 61.0 67.0 71.5 64.5 62.5 62.0
24ABR3