HEAT PUMP HEATING PERFORMANCE CONTINUED
INDOOR AIR
OUTDOOR COIL ENTERING AIR TEMPERATURES ° F C)
--- 3 ( --- 1 9 . 4 ) 7 ( ---13.9) 17 ( ---8.3) 27 ( ---2.8) 37 (2.8) 47 (8.3) 57 (13.9) 67 (19.4)
EDB
°F (°C)
CFM
Capacity MBtuh
Tot al
Sys.
KW†
Capacity MBtuh
Tot al
Sys.
KW†
Capacity MBtuh
Tot al
Sys.
KW†
Capacity MBtuh
Tot al
Sys.
KW†
Capacity MBtuh
Tot al
Sys.
KW†
Capacity MBtuh
Tot al
Sys.
KW†
Capacity MBtuh
Tot al
Sys.
KW†
Capacity MBtuh
Tot al
Sys.
KW†
Tot al Integ* To ta l Integ* Tota l Integ* Tot al Integ* To ta l Integ* Tot al Integ* To ta l Integ* Tot al Integ*
25HCB360A30 Outdoor Section With FY4ANF060 Indoor Section
65
(18.3)
1750 25.07 23.07 3.86 30.90 28.40 4.00 37.17 33.89 4.16 43.81 38.91 4.34 51.11 46.51 4.54 59.85 59.85 4.79 68.95 68.95 5.02 78.00 78.00 5.31
2000 25.62 23.57 3.93 31.49 28.94 4.06 37.79 34.45 4.20 44.47 39.50 4.36 51.96 47.28 4.54 60.88 60.88 4.74 69.47 69.47 4.95 78.33 78.33 5.20
2250 26.13 24.04 4.01 32.03 29.44 4.13 38.34 34.96 4.26 45.07 40.03 4.40 52.72 47.97 4.57 61.49 61.49 4.73 69.75 69.75 4.92 77.76 77.76 5.13
70
(21.1)
1750 24.34 22.40 4.03 30.22 27.77 4.19 36.54 33.32 4.36 43.21 38.37 4.55 50.41 45.87 4.76 58.98 58.98 5.03 68.13 68.13 5.26 77.06 77.06 5.56
2000 24.89 22.90 4.10 30.80 28.30 4.24 37.17 33.89 4.40 43.87 38.96 4.57 51.17 46.57 4.75 60.00 60.00 4.97 68.71 68.71 5.18 77.50 77.50 5.44
2250 25.40 23.37 4.18 31.34 28.80 4.31 37.72 34.39 4.45 44.46 39.49 4.60 51.85 47.19 4.77 60.72 60.72 4.95 69.06 69.06 5.15 77.77 77.77 5.39
75
(23.9)
1750 23.57 21.68 4.21 29.50 27.11 4.38 35.86 32.70 4.57 42.56 37.80 4.77 49.72 45.25 4.99 57.81 57.81 5.26 67.28 67.28 5.51 76.15 76.15 5.82
2000 24.12 22.19 4.29 30.09 27.65 4.44 36.50 33.28 4.60 43.24 38.40 4.78 50.48 45.93 4.98 58.94 58.94 5.21 67.93 67.93 5.43 76.69 76.69 5.70
2250 24.63 22.66 4.37 30.63 28.15 4.51 37.07 33.80 4.66 43.83 38.93 4.82 51.15 46.54 5.00 59.80 59.80 5.19 68.35 68.35 5.40 76.95 76.95 5.64
HEATING IN DOOR
MODEL
CAPACITY POWER FURNACE M O DEL
*FY5BNB060 1.00 1.00
FB4CNF060 0.95 0.97
FB4CNF060 0.98 1.00
FE4ANB006 0.98 0.95
FV4BNB006 0.98 0.95
FX4CN(B,F)060 0.98 0.95
FX4DN(B,F)061 0.99 0.94
FY4ANB060 1.00 1.00
CAP**6021A** 0.97 0.99
CAP**6024A** 0.98 0.97
CAP**6025A** 0.98 0.97
CNPH*6024A** 0.98 0.98
CNPH*6124A** 0.98 0.98
CNPV*6024A** 0.98 0.98
CNPV*6124A** 1.00 0.97
CSPH*6012A** 0.98 0.97
CAP**6021A** 0.94 0.96 58CV(A,X)110--- 20
CNPH*6024A** 0.96 0.99 58CV(A,X)110 ---20
CNPH*6124A** 0.98 0.99 58CV(A,X)110 ---20
CSPH*6012A** 0.96 0.97 58CV(A,X)110---20
CAP**6024A** 0.96 0.97 58CV(A,X)135--- 22
CNPH*6024A** 0.95 0.97 58CV(A,X)135 ---22
CNPH*6124A** 0.98 0.97 58CV(A,X)135 ---22
CNPV*6024A** 0.95 0.97 58CV(A,X)135--- 22
CNPV*6124A** 0.98 0.96 58CV(A,X)135--- 22
CSPH*6012A** 0.96 0.96 58CV(A,X)135---22
HEATING IN DOOR
MODEL
CAPACITY POWER FURNACE M O DEL
CAP**6024A** 0.96 0.96 58CV(A,X)155--- 22
CNPH*6024A** 0.95 0.96 58CV(A,X)155 ---22
CNPH*6124A** 0.98 0.96 58CV(A,X)155 ---22
CNPV*6024A** 0.95 0.96 58CV(A,X)155--- 22
CNPV*6124A** 0.98 0.95 58CV(A,X)155--- 22
CSPH*6012A** 0.96 0.95 58CV(A,X)155---22
CNPH*6024A** 0.99 1.03 58HDV080--- ---20
CNPH*6124A** 1.00 1.01 58HDV080--- ---20
CNPV*6024A** 0.98 1.00 58HDV080--- --- 20
CNPV*6124A** 1.00 1.00 58HDV080--- --- 20
CSPH*6012A** 0.98 0.99 58HDV080--- --- 20
CAP**6025A** 0.98 1.01 58HDV100--- ---20
CNPH*6024A** 0.98 1.01 58HDV100--- ---20
CNPH*6124A** 0.99 1.00 58HDV100--- ---20
CNPV*6024A** 0.98 1.01 58HDV100--- --- 20
CNPV*6024A** 0.98 1.00 58HDV100--- --- 20
CNPV*6124A** 0.98 0.98 58HDV100--- --- 20
CNPV*6124A** 0.99 0.99 58HDV100--- --- 20
CSPH*6012A** 0.98 0.99 58HDV100--- --- 20
CNPH*6024A** 0.97 1.01 58ME(B,C)080 ---16
CNPH*6124A** 0.98 1.00 58ME(B,C)080 ---16
CSPH*6012A** 0.98 1.01 58ME(B,C)080--- 16
CAP**6021A** 0.97 0.99 58ME(B,C)100--- 20
CNPH*6024A** 0.97 0.99 58ME(B,C)100 ---20
CNPH*6124A** 0.97 0.97 58ME(B,C)100 ---20
CSPH*6012A** 0.97 0.98 58ME(B,C)100--- 20
HEATING IN DOOR
MODEL
CAPACITY POWER FURNACE M O DEL
CAP**6024A** 0.97 0.98 58ME(B,C)120--- 20
CNPH*6024A** 0.97 0.98 58ME(B,C)120 ---20
CNPH*6124A** 0.10 0.10 58ME(B,C)120 ---20
CNPV*6024A** 0.97 0.98 58ME(B,C)120--- 20
CNPV*6124A** 0.98 0.96 58ME(B,C)120--- 20
CSPH*6012A** 0.97 0.97 58ME(B,C)120--- 20
CNPH*6124A** 0.99 1.02 58MV(B,C)080---20
CNPH*6124A** 0.98 1.01 58MV(B,C)100---20
CNPH*6124A** 0.98 0.99 58MV(B,C)120---20
CNPV*6124A** 0.98 0.99 58MV(B,C)120 ---20
CAP**6021A** 0.97 0.99 58PH*090---16
CNPH*6024A** 0.97 1.00 58PH*090---16
CSPH*6012A** 0.97 0.98 58PH*090--- 16
CAP**6021A** 0.98 0.99 58PH*110---20
CNPH*6024A** 0.97 0.98 58PH*110---20
CNPH*6124A** 0.98 0.97 58PH*110---20
CSPH*6012A** 0.97 0.97 58PH*110--- 20
CAP**6024A** 0.97 0.99 58PH*135---20
CNPH*6024A** 0.97 0.99 58PH*135---20
CNPH*6124A** 0.98 0.98 58PH*135---20
CNPV*6024A** 0.97 0.99 58PH*135--- 20
CNPV*6124A** 0.98 0.97 58PH*135--- 20
CSPH*6012A** 0.97 0.97 58PH*135--- 20
CNPH*6024A** 0.97 0.99 58VLR120---20
CSPH*6012A** 0.97 0.97 58VLR120--- 20
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
* The Btuh heating capacity values shown are net integrated values from which the defrost effect has been subtracted. The Btuh heating from supplement heaters should be added to those values to obtain total system capaci ty.
{ The kW values include the compressor, outdoor fan motor, and indoor blower motor. The kW from supplement heaters should be added to these values to obtain total system kilowatts.