7
ELECTRICAL DATA
U N I T S I Z E ---
SERIES,
VOLTAGE
V/PH
OPER VOLTS* COMPR FAN
MCA
MIN
WIRE
SIZE†
MIN
WIRE
SIZE†
MAX
LENGTH
ft (m)‡
MAX
LENGTH
ft (m)‡
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
18--- 30
208/230/1 253 197
48.0 9.0 0.7 11.9 14 14 66 (20.1) 62 (18.9) 20
24--- 30 58.3 12.8 0.7 16.7 14 14 47 (14.3) 45 (13.7) 25
30--- 30 77.0 16.0 0.8 20.8 12 12 60 (18.3) 57 (17.4) 30
36--- 30 79.0 17.1 0.9 22.3 12 12 56 (17.1) 53 (16.2) 35
42--- 30 109.0 19.9 1.2 26.0 10 10 77 (23.5) 73 (22.3) 40
48--- 30 117.0 27.3 1.2 35.4 8 8 88 (26.8) 84 (25.6) 50
60--- 31 134.0 26.3 1.2 34.1 8 8 91 (27.7) 87 (26.5) 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310 ---16 of the NEC (ANSI/NFPA 70). T he ampacity of non ---metallic---sheathed cable (NM),
trade name ROMEX, shall be that of 60_C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated ( no--- pla ted), 60 or 75_C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA
70).
} Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u se .
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d Ro t o r A m p s
M C A --- Minimum Circuit Amps
RLA --- RatedLoadAmps
NOTE: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requiremen ts of ASHRAE Stan dards 90.1
A--WEIGHTED SOUND POWER
UNIT SIZE---SERIES, VOLTAGE
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
18---30 73 58.5 62.5 67.0 67.5 65.5 62.5 53.5
24---30 72 54.5 63.0 66.5 66.0 64.0 60.5 51.5
30---30 73 57.0 63.5 68.0 69.0 65.0 61.0 52.5
36---30 70 54.5 62.0 63.5 64.5 63.0 60.0 51.5
42---30 73 55.0 60.0 64.0 67.5 61.5 60.0 55.0
42---30 73 55.0 60.0 64.0 67.5 61.5 60.0 55.0
48---30 74 57.5 64.5 67.5 69.5 66.5 61.0 53.0
60---31 74 53.5 63.0 67.5 70.0 63.5 60.0 55.5
NOTE: Tested in accordance with AHRI Stan dard 270---2008 (not listed in AHRI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---SERIES, VOLTAGE REQUIRED SUBCOOLING _F(_C)
18---30 10 (5.6)
24---30 12 (6.7)
30---30 12 (6.7)
36---30 10 (5.6)
42---30 11 (6.1)
48---30 11 (6.1)
60---31 12 (6.7)
25HCB3