70
Step 4: L1 off, L2 blinks, L3 and L4 off.
L5 will turn on if the selected temperature is between
–5°C and 15°C.
Step 5: L1 off, L2 blinks, L3 off, L4 blinks.
L5 will always turn on.
Step 6: L1 off, L2 and L3 blink, L4 off.
L5 will turn on if there is 24Vca in the IN1 terminal
(Pressostat input).
Step 7: L1 off, L2, L3 and L4 blink.
L5 will turn on after 1 second and will remain on during 5
seconds. The IN1-OUT1 contact will remain closed while
L5 is ON (Contact for the compressor contactor
handling).
Power voltage: 24V ±15%, 50Hz or 60Hz.
Maximum consumption: 200mA
Operating temperature: -20°C a +60°C
Digital inputs (IN1, IN4, IN5, IN6)
Maximum permanent voltage 80Vca ou 60Vcc
Input current 0,65mA @ 24Vca
(for IN1 add current in OUT1)
Maximum de-activation voltage 1Vca
Minimum activation voltage 4Vca
Answer time 0 to 24Vca 0,25s
Answer time 24 to 0Vca 1s
Analog inputs (A3,A4) Sensor type NTC de 5KW @ 25°C
Temperature setting input
Temperature setting Lineal potentiometer
Saídas digitais
• OUT1
Maximum voltage 80Vca
Maximum current 16A resistive charge
• OUT2
Maximum voltage 250Vca
Maximum current 16A resistive charge
Control board dimensions 121 x 123 mm
Control front dimensions 100 x 100 mm
Temperature setting dimensions 45 x 35 mm, high: 35mm with handle
included
Long cable in front of control 300mm
Long temperature setting cable 250mm
Step 8: L1 blinks, L2, L3 and L4 off.
L5 will turn on after 1 second and will remain in this
status. The IN2-OUT2 contact will remain closed while
L5 is ON (Contact to handle the solenoid valve).
Step 9: L1 blinks, L2 and L3 off, L4 blinks.
L5 will turn on if there is 24 Vca in the IC3 terminal
(Input for the remote control contact).
Step 10: L1 blinks, L2 off, L3 blinks, L4 off.
L5 will turn on if there is 24 Vca in the IC4 terminal
(Input for the ON/OFF remote control).
SPECIFICATIONS: