5.6 - ELECTRIC DATA
IMPORTANT NOTES
Data from the supplier's technical catalog.
1 - RLA, KW, RLA TOTAL and KW TOTAL refer to nominal operation data with the unit in operation.
Suction temperature: 45°F (7.2°C) and condensation temperature: 130°F (54.4°C) - ARI conditions.
2 - MOPA values shown in the table were calculated taking into consideration the maximum operation values of the unit.
3 - Values show in the KVAr column be dimensioned to the compressors when is necessary to correct the POWER FACTOR to 0,92.
4 - All compressors are Scroll.
Legends
RLA Nominal Current (Rated Load Amps).
LRA Locked Rotor Current (Locked Rotor Amps).
MOPA Maximum recommended capacity for the protection of the fuse against short circuit.
KW Consumed Rated Power.
FP Power Factor (without correction to 0.92)
KVAr Recommended reactive power for the sizing of the bank of capacitors(0.92).
Fan
Technical Data
QTDE RLA [A] P [CV] KW Total
1 1,3 1/6 0,123
1 1,3 1/6 0,123
1 1,3 1/6 0,123
1 1,3 1/6 0,123
1 2,2 1 0,79
1 2,2 1 0,75
30AJ
UNIT
04
05
10
Voltage [ V ] / [Hz]
Power supply / Frequency
NOMINAL MIN. MAX
220/60 198 242
380/60 342 418
220/60 198 242
380/60 342 418
220/60 198 242
380/60 342 418
Compressor
Technical Data
RLA [A] LRA [A] KW FP KVAr
ZR47
14,3 91,0 4,2 0,76 2,5
7,2 46,0 4,2 0,87 1
ZR57
ZR57
17,2 124,0 5 0,76 2,5
8,2 59,6 5 0,42 1
ZR72
125
33,1 237,0 10,8 0,86 5
19,8 160,0 10,8 0,83 5
144
Complementary Technical Data
Circuit A
RLA Total [A] KW Total [W] MOPA [A]
15,6 4,3 25
8,5 4,3 16
18,5 5,1 25
9,5 5,1 25
38,3 11,5 50
22,0 11,5 40