7.6 - ELECTRICAL CIRCUIT
7.6.1 - Unit 30AJ 220V
COLORS CODIFICATION
AMR - YELLOW
AZL - BLUE
BRC - WHITE
CNZ - GRAY
LRJ - ORANGE
MRM - BROWN
PRT - BLACK
ROS - PINK
VIO - VIOLET
VRD - GREEN
VRM - RED
NOTES:
1 - CONNECT ELECTRICAL BRIDGE BETWEEN TERMINALS 5 AND IN4, IF WANT TO WORK IN LOW
TEMPERATURE (–7°C).
2 - CONNECT ELECTRICAL BRIDGE BETWEEN TERMINALS 5 AND IN6, IF IS DESIRED TO COMMAND
THE UNIT AT A DISTANCE BY THE ICD, IF:
ICD OPENED - BLINKING SLOW LED N°1.
ICD CLOSED - BLINKING FAST LED N°1.
IT MUST BE CONNECTED BETWEEN TERMINALS 5 AND 6, FLOW SWITCH, NORMALLY OPEN
CONTACT PUMP AND REMOTE SWITCH.
3 - IF THE UNIT TURN OFF BY SOME REASON, THEN THE LED N°3 WILL BE ILUMINATED INDICATING
THAT THIS UNIT WILL TURN ON IN THE NEXT 4 MINUTES, 30 SEC, BEFORE THE FINISHING OF THE
MINUTES, THE LED N°3 WILL BEGIN BLINK ANNOUCING THE CONCLUSION OF TIMER.
4 - IF THIS TEMPERATURE IS SETTED IN 2°C MINIMUM (WITHOUT ELECTRICAL BRIDGE BETWEEN
TERMINALS 5 AND IN4) AND PUT THE PA TO LESS OF 2°C , THE UNIT WILL BE INTERRUPTED BY
FREEZING.
LEGEND:
BC - CONTROL TERMINAL BLOCK
BF - POWER TERMINAL BLOCK
COMP - COMPRESSOR
CAP - CAPACITOR
CB - PUMP CONTACT
CC - COMPRESSOR CONTACTOR
CH - CRANCKASE HEATER
F - FUSE
FS - FLOW SWITCH
HPS - HIGH PRESSURE SWITCH
ICD - REMOTE SWITCH
C - COMMON TERMINAL
BS - SENSOR TERMINAL BLOCK
PTC - COMPRESSOR TERMIC PROTECTOR (ONLY IN SOME MODELS)
LPS - LOW PRESSURE SWITCH
PC - DISPLAY (IHM)
PLC - ELECTRONIC BOARD
TR - TRANSFORMER
OFM - OUTDOOR FAN MOTOR
VS - VALVE SOLENOID
RT1 - LIVING WATER TEMPERATURE SENSOR
RT2 - ENTERING WATER TEMPERATURE SENSOR
PA - SET POINT TEMPERATURE ADJUST
*  -  ACESSORY
-- -- --  CONNECT MADE IN FIELD
ELECTRICAL DIAGRAM
NOTE