Carrier 30RB060-390 - Page 21

Carrier 30RB060-390
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
7169.08
282.25[]
2806.54
110.49[]
800.00
31.50[]
CG
x
930.95
36.652[]
1885.22
74.221[]
PIPING ENTRANCE AREA3222.17
126.86[]
1348.58
53.09[]
1256.59
49.47[]
2690.32
105.92[]
2236.08
88.03[]
760.39
29.94[]
1447.8
[57.0]
400.00
15.75[]
240.00
9.45[]
CG
y
200.00
7.87[]
100.00
3.94[]
RIGGING HOLE
38.00
1.50[]
864.00
34.02[]
408.89
16.10[]
UNIT MOUNTING
1981.65
78.02[]
UNIT MOUNTING
2794.35
110.01[]
UNIT MOUNTING
1575.30
62.02[]
408.89
16.10[]
2281.37
89.82[]
437.86
17.24[]
437.86
17.24[]
200.00
7.87[]
200.00
7.87[]
1990.54
78.37[]
UNIT MOUNTING
2156.30
84.89[]
39.89
1.57
[]
800.00
31.50[]
2016.54
79.39[]
759.89
29.92[]
2438.40
[96.00]
938.35
36.94[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
WEIGHT
CU/CU
lb/kg
WEIGHT
MCHX
lb/kg
CENTER OF GRAVITY
CGx
MM [INCH]
CGy
MM [INCH]
30RB-210
13734
6243
15181
6901
12772
5793
3528
[138.90]
917
[36.10]
30RB-225
14067
6394
15514
7052
13093
5937
3588
[141.26]
906
[35.67]
CIRCUIT C
COMPRESSORS
POWER BOX 2
230V ONLY
CKT C
POWER BOX 1 & 2
(PEB)
ALL VOLTAGES
LEAVING WATER
6" VICTAULIC
ENTERING WATER
6" VICTAULIC
COOLER VENT
1/4" NPT
COOLER DRAIN
3/4" NPT
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
A
A
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
POWER BOX 1
230V CKT B
380V,460V,575V
CKT A,B,C
COIL SERVICE AREA
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
PEB1 230V DUAL POINT
380V,460V,575V DUAL & SINGLE POINT
PEB2 230V DUAL POINT
380V,460V,575V DUAL POINT
SEE DETAIL
B
VIEW-A-A
DETAIL B
SCALE 1:4
22.2[.87]
MOUNTING HOLE
POWER BOX
230V ONLY (CKT A)
SCROLLING MARQUEE
DISPLAY
FIELD CONTROL WIRING
FAN ELECTRICAL BOX
(FEB)
ALL VOLTAGES
AIR FLOW
COIL SERVICE AREA
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
(DUAL POINT 230V ONLY)
(DUAL POWER NFD
CIRCUIT B 380,460,
575V ONLY)
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
2. Temperature relief devices located on suction line, liquid line
and filter drier of each circuit and have
1
/
4
flare connection.
3. Dimensions are in mm [inches].
4. Allow 8 ft (2.4 m) of service access on either side of unit for
condenser coil removal.
a30-4716
MCHX — Microchannel Condenser Coil
Fig. 17 — 30RB210, 225 Air-Cooled Chiller Dimensions