63
Table 10A — 30RB060-190 Electrical Data — Single Point Units (cont)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied to the unit
terminals is not below or above the listed minimum and maximum limits. Maximum
allowable phase imbalance is: voltage, 2%; amps 10%.
2. All units and modules have single point primary power connection. (Each unit or mod-
ule requires its own power supply.) Main power must be supplied from a field-supplied
disconnect.
3. Cooler heater is wired into the control circuit so it is always operable as long as the
power supply disconnect is on, even if any safety device is open.
4. For MCA that is less than or equal to 380 amps, 3 conductors are required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
5. Wiring for main field supply must be rated 75 C minimum. Use copper for all units.
a. Incoming wire size range for the terminal block is no. 4 AWG to 500 kcmil.
b. Incoming wire size range of non-fused disconnect with MCA up to 599.9 amps is
3/0 to 500 kcmil.
c. Incoming wire size range of non-fused disconnect with MCA from 600 to
799.9 amps is 1/0 to 500 kcmil.
d. Incoming wire size range of non-fused disconnect with MCA from 800 to
1199.9 amps is 250 kcmil to 500 kcmil.
6. Hydronic pump packages are not available as a factory-installed option for units
30RB210-390.
7. Power draw includes both crankcase heaters and cooler heaters (where used). Each
compressor has a crankcase heater which draws 56 watts of power. Units ordered with
the cooler heater option have 1 (060-150) or 2 (160-300) cooler heaters, 825 watts
each.
UNIT 30RB
UNIT VOLTAGE 7.5 HP PUMP, 1750/3450 RPM 10 HP PUMP, 3450 RPM 15 HP PUMP, 3450 RPM
V-Hz (3 Ph)
Supplied MCA MOCP ICF
Rec Fuse
Size
MCA MOCP ICF
Rec Fuse
Size
MCA MOCP ICF
Rec Fuse
Size
Min Max XL XL XL XL XL XL XL XL XL
060
208/230-60 187 253 313.5 350 708.5 350 316.5 350 716.4 350 — — — —
380-60 342 418 163.2 200 376.9 175 164.9 200 381.3 175 — — — —
460-60 414 506 138.0 150 313.6 150 139.4 150 317.2 150 — — — —
575-60 518 633 110.5 125 254.0 125 111.6 125 256.9 125 — — — —
070
208/230-60 187 253 356.7 450 802.7 400 359.7 450 810.6 400 — — — —
380-60 342 418 187.8 225 442.8 225 189.5 225 447.2 225 — — — —
460-60 414 506 158.0 175 367.5 175 159.4 200 371.1 175 — — — —
575-60 518 633 127.9 150 296.7 150 129.0 150 299.6 150 — — — —
080
208/230-60 187 253 388.5 450 783.5 450 391.5 450 791.4 450 403.2 450 807.6 450
380-60 342 418 201.6 225 415.3 225 203.3 225 419.7 225 210.3 225 428.5 225
460-60 414 506 170.7 200 346.3 200 172.1 200 349.9 200 177.6 200 357.2 200
575-60 518 633 136.7 150 280.2 150 137.8 150 283.1 150 142.6 150 288.9 150
090
208/230-60 187 253 455.6 500 901.6 500 458.6 500 909.5 500 470.3 500 925.7 500
380-60 342 418 239.2 250 494.3 250 240.9 250 498.7 250 247.9 250 507.5 300
460-60 414 506 201.5 225 411.0 225 202.9 225 414.6 225 208.4 250 421.9 225
575-60 518 633 162.7 175 331.5 175 163.8 175 334.4 175 168.6 200 340.2 200
100
208/230-60 187 253 494.0 500 940.0 500 497.0 500 947.9 600 508.7 600 964.1 600
380-60 342 418 261.0 300 516.1 300 262.7 300 520.5 300 269.7 300 529.3 300
460-60 414 506 219.3 250 428.8 250 220.7 250 432.4 250 226.2 250 439.7 250
575-60 518 633 178.1 200 346.9 200 179.2 200 349.8 200 184.0 200 355.6 200
110
208/230-60 187 253 530.6 600 976.6 600 533.6 600 984.5 600 545.3 600 1000.7 600
380-60 342 418 277.6 300 532.7 300 279.3 300 537.1 300 286.3 300 545.9 300
460-60 414 506 234.2 250 443.7 250 235.6 250 447.3 250 241.1 250 454.6 250
575-60 518 633 188.9 200 357.7 200 190.0 200 360.6 200 194.8 225 366.4 225
120
208/230-60 187 253 600.1 700 1046.1 700 603.1 700 1054.0 700 614.8 700 1070.2 700
380-60 342 418 316.9 350 572.0 350 318.6 350 576.4 350 325.6 350 585.2 350
460-60 414 506 266.3 300 425.8 300 267.7 300 479.4 300 273.2 300 486.7 300
575-60 518 633 216.3 225 385.1 250 217.4 250 388.0 250 222.2 250 393.8 250
130
208/230-60 187 253 648.7 700 1094.6 700 651.7 700 1102.5 700 663.4 700 1118.7 700
380-60 342 418 340.0 350 595.1 350 341.7 350 599.5 350 348.7 350 608.3 400
460-60 414 506 286.6 300 496.1 300 288.0 300 499.7 300 293.5 300 507.0 300
575-60 518 633 231.4 250 400.3 250 232.5 250 403.2 250 237.3 250 409.0 250
150
208/230-60 187 253 706.3 800 1152.2 800 709.3 800 1160.1 800 721.0 800 1176.3 800
380-60 342 418 372.7 400 627.8 400 374.4 400 632.2 400 381.4 400 641.0 400
460-60 414 506 313.3 350 522.8 350 314.7 350 526.4 350 320.2 350 533.7 350
575-60 518 633 254.5 300 423.4 300 255.6 300 426.3 300 260.4 300 432.1 300
160
208/230-60 187 253 766.8 800 1212.7 800 769.8 800 1220.6 800 781.5 800 1236.8 800
380-60 342 418 402.4 450 657.5 450 404.1 450 661.9 450 411.1 450 670.7 450
460-60 414 506 339.0 350 548.5 350 340.4 350 552.1 350 345.9 350 559.4 400
575-60 518 633 274.0 300 442.8 300 275.1 300 445.7 300 279.9 300 451.5 300
170
208/230-60 187 253 824.4 1000 1270.3 1000 827.4 1000 1278.2 1000 839.1 1000 1294.4 1000
380-60 342 418 435.1 450 690.2 450 436.8 450 694.6 450 443.8 450 703.4 500
460-60 414 506 365.7 400 575.2 400 367.1 400 578.8 400 372.6 400 586.1 400
575-60 518 633 297.1 300 465.9 300 298.2 300 468.8 350 303.0 350 474.6 350
190
208/230-60 187 253 942.5 1000 1388.4 1000 945.5 1000 1396.3 1000 957.2 1000 1412.5 1000
380-60 342 418 497.5 500 752.5 500 499.2 500 756.9 600 506.2 600 765.7 600
460-60 414 506 418.1 450 627.6 450 419.5 450 631.2 450 425.0 450 638.5 450
575-60 518 633 339.6 350 508.4 350 340.7 350 511.3 350 345.5 350 517.1 350
AWG — American Wire Gage MOCP — Maximum Overcurrent Protection
ICF — Instantaneous Current Flow XL — Across-the-Line Start
MCA — Minimum Circuit Amps