Carrier 30RB060-390 - Page 7

Carrier 30RB060-390
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
2281.37
89.82[]
PS
x
PD
y
PS
y
521.16
20.52[]
386.88
15.23[]
408.89
16.10[]
UNIT MOUNTING1575.30
62.02[]
408.90
16.10[]
PD
x
2393.08
94.22[]
2236.08
88.03[]
1447.8 [57.00]
PD
z
PS
z
CG
y
CG
x
45.00
1.77[]
200.00
7.87[]
100.00
3.94[]
RIGGING HOLE
19.00
0.75[]
296.47
11.67[]
PIPING ENTRANCE AREA
1692.75
66.64[]
403.76
15.90[]
788.34
31.04[]
864.00
34.02[]
190.00
7.48[]
UNIT MOUNTING
2159.89
85.035[]
246.36
9.70[]
336.50
13.25[]
38.09
1.50[]
2438.40
[96.00]
949.14
37.37[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
MAX WEIGHT
CU/AL PUMP
lb/kg
WEIGHT
CU/CU
lb/kg
MAX WEIGHT
CU/CU PUMP
lb/kg
WEIGHT
MCHX
lb/kg
MAX WEIGHT
MCHX PUMP
lb/kg
CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CGx
MM [INCH]
CGy
MM [INCH]
X
.25
Y
.25
Z
.25
X
.25
Y
.25
Z
.25
30RB-080
1206
[47.48]
1012
[39.84]
675.6
[26.6]
309.9
[12.2]
353.1
[13.9]
381.0
[15.0]
497.8
[19.6]
170.2
[6.7]
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
FAN ELECTRICAL BOX
(230V ONLY)
(FEB)
CIRCUIT
A
COMPRESSORS
CIRCUIT
B
COMPRESSORS
COIL SERVICE AREA
COIL SERVICE AREA
NO PUMP PACKAGE
ENTERING WATER
4" VICTAULIC
(SEE NOTE 4)
COOLER VENT
1/4" NTP
PUMP PACKAGE
LEAVING WATER
4" VICTAULIC
COOLER DRAIN
3/4" NPT
PUMP PACKAGE
ENTERING WATER
4" VICTAULIC
SEE DETAIL
A
COOLER TUBE
SERVICE AREA
DETAIL
A
SCALE 11:32
22.2[.87]
MOUNTING HOLE
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
SCROLLING MARQUEE
DISPLAY
POWER BOX 230V
CONTROL/POWER BOX
380V,460V,575V
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
AIR FLOW
FIELD CONTROL WIRING
4600
2091
5523
2511
5082
2310
6005
2730
4267
1934
5190
2355
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from
solid surface.
2. All pumps have drains located at the
bottom of volute for draining.
3. Temperature relief devices located on
suction line, liquid line and filter drier
of each circuit and have
1
/
4
flare con-
nection.
4. Units without a pump package have
the same leaving water connection, Y
and Z dimensions (entering water),
and Pump Discharge X dimensions
as units with a pump package.
5. Dimensions are in mm [inches].
6. Allow 8 ft (2.4 m) of service access on
either side of unit for condenser coil
removal.
a30-4733
MCHX — Microchannel Condenser Coil
Fig. 3 — 30RB080 Air-Cooled Chiller Dimensions