EasyManua.ls Logo

Carrier 35E - Page 5

Carrier 35E
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
Table 2 35E Basic Pressure Data
LEGEND
*Minimums are for all except CCN controls, which may be lower. Minimum for DDC by
others is to be provided by the control’s provider.
†A minimum 0.03 in. wg discharge static pressure is required to set the flow switch in the
electric heater.
**Maximum discharge temperatures with electric heat are set at 120 F by the National
Electric Code. Max kW shown assumes 55 F entering air and is limited by unit’s selected
voltage, phase, max capacity and design (see Electrical Data in the Product Data cata-
log). Min cfm for electric heat is based on UL/ETL listings. (Diffuser) performance will
likely be poor at this low flow rate.) The ASHRAE (American Society of Heating, Refrig-
eration and Air Conditioning Engineers) Handbook of Fundamentals does not recom-
mend a discharge temperature exceeding 90 F for satisfactory air mixing and comfort.
††Max. kW is limited by design.
NOTES:
1. To obtain Total Pressure (Pt), add the Velocity Pressure for a given cfm to the Static
Pressure drop ( P
S
) of the desired configuration.
Example: Pt for a Size 8 Basic Unit at 925 cfm = 0.39 + 0.17 = 0.56
2. The electric heat max kW is based on 3 phase power. For more details, refer to the air
terminal selection program.
Table 3A 35E Heater Power Wiring and
Fuse Sizing (Single Phase, 60 Hz)
LEGEND
*Values based on 75 C copper wire.
Table 3B 35E Heater Power Wiring and
Fuse Sizing (3 Phase, 60 Hz)
LEGEND
*Recommended minimum wire size.
INLET
SIZE (in.)
(Area)
CFM
MIN AIRFLOW (Cfm)*
ELECTRIC HEAT**
MAX kW
AT 55 F EAT
MINIMUM INLET STATIC PRESSURE (Unit and Heat Pressure Drop)
Cooling Only or
Cooling with Hot Water
Electric
Heat
Velocity Press
( V
PS
)
Basic Unit
( P
S
)
Basic + 1 Row
Coil ( P
S
)
Basic + 2 Row
Coil ( P
S
)
Basic + 3 Row
Coil ( P
S
)
Basic + 4 Row
Coil ( P
S
)
Basic + Heater
( P
S
)
55
50
or
0
55
1.1 0.02 0.00 0.00 0.01 0.01 0.01 0.00
4 110 2.3 0.10 0.01 0.02 0.03 0.03 0.04 0.01
(0.09) 170 3†† 0.23 0.02 0.04 0.06 0.08 0.10 0.02
230 3†† 0.43 0.03 0.07 0.11 0.15 0.18 0.03
85
75
or
0
85
1.7 0.02 0.00 0.01 0.02 0.02 0.03 0.00
5 170 3.5 0.09 0.02 0.04 0.06 0.08 0.10 0.02
(0.14) 265 5†† 0.23 0.04 0.10 0.15 0.20 0.24 0.04
360 5†† 0.43 0.08 0.18 0.27 0.36 0.45 0.08
100
110
or
0
110
2.1 0.02 0.01 0.01 0.02 0.03 0.03 0.01
6 240 4.9 0.09 0.04 0.08 0.12 0.16 0.20 0.04
(0.20) 380 7.5†† 0.22 0.09 0.20 0.30 0.40 0.50 0.09
520 7.5†† 0.42 0.17 0.38 0.57 0.75 0.94 0.17
140
140
or
0
140
2.9 0.02 0.01 0.01 0.02 0.03 0.04 0.01
7 330 6.8 0.09 0.04 0.08 0.12 0.16 0.20 0.04
(0.27) 525 9.5†† 0.23 0.09 0.20 0.30 0.40 0.50 0.09
710 9.5†† 0.41 0.17 0.37 0.55 0.73 0.91 0.17
190
185
or
0
190
3.9 0.02 0.01 0.02 0.03 0.05 0.06 0.01
8 440 9.1 0.09 0.04 0.12 0.19 0.25 0.32 0.04
(0.35) 675 13†† 0.21 0.09 0.27 0.44 0.60 0.76 0.09
925 13†† 0.39 0.17 0.51 0.82 1.13 1.43 0.17
240
240
or
0
240
4.9 0.02 0.01 0.02 0.03 0.04 0.05 0.01
9 550 11.3 0.08 0.07 0.12 0.17 0.22 0.27 0.07
(0.44) 875 16†† 0.21 0.17 0.31 0.44 0.57 0.69 0.17
1200 16†† 0.40 0.32 0.59 0.83 1.07 1.31 0.32
300
290
or
0
300
6.2 0.02 0.01 0.02 0.04 0.05 0.07 0.01
10 675 13.9 0.08 0.04 0.12 0.20 0.27 0.35 0.04
(0.55) 1075 21†† 0.20 0.10 0.31 0.50 0.69 0.89 0.10
1450 21†† 0.36 0.17 0.56 0.91 1.26 1.62 0.17
425
420
or
0
425
8.7 0.01 0.01 0.02 0.04 0.06 0.07 0.01
12 1000 20.6 0.08 0.04 0.14 0.22 0.31 0.40 0.04
(0.78) 1550 30†† 0.19 0.09 0.33 0.54 0.75 0.96 0.09
2100 30†† 0.34 0.17 0.60 0.99 1.37 1.76 0.17
580
580
or
0
580
11.9 0.01 0.01 0.02 0.04 0.05 0.06 0.01
14 1375 28.3 0.07 0.04 0.13 0.21 0.28 0.36 0.04
(1.07) 2125 36†† 0.17 0.10 0.31 0.49 0.68 0.86 0.10
2900 36†† 0.31 0.19 0.57 0.92 1.26 1.60 0.19
750
740
or
0
750
15.4 0.01 0.01 0.02 0.04 0.06 0.07 0.01
16 1775 36†† 0.06 0.04 0.14 0.22 0.31 0.40 0.04
(1.40) 2725 36†† 0.14 0.09 0.32 0.53 0.73 0.94 0.09
3700 36†† 0.25 0.17 0.59 0.97 1.35 1.73 0.17
1800
1400
or
0
1800
36†† 0.02 0.01 0.05 0.09 0.13 0.16 0.01
22 3300 36†† 0.07 0.04 0.17 0.30 0.42 0.55 0.04
(2.63) 5200 36†† 0.16 0.09 0.43 0.74 1.05 1.36 0.09
7100 36†† 0.31 0.17 0.81 1.38 1.95 2.53 0.17
CCN Carrier Comfort Network® P
S
Thedifferenceinstaticpressure
from inlet to discharge with damper
fully open
DDC Direct Digital Controls
EAT Entering Air Temperature
UL Underwriters Laboratories V
PS
Change in velocity pressure
HEATER
SIZE (kW)
BTUH
120 V 208/240 V 277 V
Heater
FLA
AWG*
Heater
FLA
AWG*
Heater
FLA
AWG*
0.5 1,707 4.2 14 2.1 14 1.8 14
1.0 3,413 8.3 14 4.2 14 3.6 14
2.0 6,826 16.7 10 8.3 14 7.2 14
3.0 10,239 25.0 8 12.5 12 10.8 14
4.0 13,652 33.3 8 16.7 10 14.4 12
5.0 17,085 41.7 5 20.8 10 18.1 10
6.0 20,478 50.0 5 25.0 8 21.7 10
7.0 23,898 58.3 4 29.2 8 25.3 8
8.0 27,304 66.7 4 33.3 8 28.9 8
9.0 30,717 75.0 3 37.5 6 32.6 8
10.0 34,130 83.3 2 41.7 6 36.1 6
11.0 37,130 91.7 2 45.8 6 39.7 6
12.0 40,956 100.0 1 50.0 6 43.3 6
AWG American Wire Gage
FLA Full Load Amps
HEATER
SIZE (kW)
BTUH
208 V 480 V
Heater FLA AWG* Heater FLA AWG*
0.5 1,707 1.4 14 0.6 10
1.0 3,413 2.8 14 1.2 10
2.0 6,826 5.6 14 2.4 10
3.0 10,239 8.3 14 3.6 10
4.0 13,652 11.1 14 4.8 10
5.0 17,085 13.9 12 6.0 10
6.0 20,478 16.7 10 7.2 10
7.0 23,898 19.4 10 8.4 10
8.0 27,304 22.2 10 9.6 10
9.0 30,717 25.0 8 10.8 10
10.0 34,130 27.8 8 12.0 10
12.0 40,956 33.3 8 14.4 12
14.0 47,782 38.8 6 16.8 12
16.0 54,608 44.4 6 19.2 10
18.0 61,434 50.0 6 21.6 10
20.0 68,260 55.5 4 24.0 10
22.0 75,086 61.1 4 26.4 8
24.0 81,912 66.6 4 28.8 8
26.0 88,738 72.3 3 31.3 8
28.0 95,564 77.8 3 33.7 8
30.0 102,390 83.4 2 36.1 6
32.0 109,216 89.0 2 38.6 6
34.0 116,042 94.5 1 41.0 6
36.0 122,868 100.1 1 43.4 6
AWG American Wire Gage
FLA Full Load Amps

Table of Contents

Related product manuals