EasyManua.ls Logo

Carrier 38AH044-084 - Dimensions - Units 38 AH044,054,064

Carrier 38AH044-084
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DUAL CKT SINGLE CKT
SUCTION
CONNECTION(S)
2
1
8
9 Dia [54 mm] 2
5
8
9 Dia [67 mm]
LIQUID
CONNECTION(S)
7
8
9 Dia [22 mm] 1
1
8
9 Dia [29 mm]
SUCTION C 28-
11
16
9 [627mm] 18-10
5
16
9 [567mm]
LIQUID D 18-10
1
16
9 [561mm] 18-10
5
16
9 [567mm]
SUCTION (Ckt A) 18-7
13
16
9 [503mm] 28-
5
8
9 [626mm]
SUCTION (Ckt B) 28-
5
8
9 [626mm]
LIQUID (Ckt A) 28-5
3
4
9 [756mm] 28-10
5
8
9 [879mm]
LIQUID (Ckt B) 28-10
5
8
9 [879mm]
NOTES:
1. The approximate operating weight of the unit is:
38AH-044--- 3259 lb [1478 kg]
38AH-044--C 3547 lb [1609 kg]
38AH-054--- 3309 lb [1501 kg]
38AH-054--C 3597 lb [1632 kg]
38AH-064--- 3565 lb [1617 kg]
38AH-064--C 3998 lb [1813 kg]
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting
unit to spring isolators. If spring isolators are used, a perimeter support channel between the unit and
the isolators is recommended.
4. One 3
5
8
9 (92 mm) diameter hole is recommended for single-entry power on size 064 (208/230-v) units.
5. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A and 2B forA-D corner weights.
6. Circled numerals in Top View refer to condenser fans by position.
Chart 1, Field Power Supply Connections
UNIT VOLTAGE Hz DIAMETER in. [mm] QTY
044 230 50 3
5
8
[92] 1
044, 054
208/230 60 3
5
8
[92] 1
346, 380/415 50 2
1
2
[63] 1
044, 054, 064 460,575,380 60 2
1
2
[63] 1
064
208/230 60 2
1
2
[63] 2
346, 380/415 50 3
5
8
[92] 1
LEGEND
C—Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
Fig. 1 Dimensions Units 38AH044,054,064
4

Table of Contents