Loading...
Chart 1, Field Power Supply Connections
UNIT
38AH
VOLTAGE Hz DIAMETER in. (mm) QUANTITY
094
208/230 60 3
5
8
(92) 2
460, 575,
380
60 3
5
8
(92) 1
346, 380/415 50 3
5
8
(92) 1
LEGEND
C—Copper Fin Coils
MTG Mounting
SAE Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
38AH-094--- 5088 lb (2308 kg)
38AH-094--C 5813 lb (2637 kg)
2. Unit must have clearances for airflow as follows:
Top Do not restrict in any way.
Ends—5ft[1524 mm]
Sides—6ft[1829 mm]
3. Mounting holes may be used to mount unit to concrete pad. They are not
recommended for mounting unit to spring isolators.
4. Two 3
5
8
9 (92-mm) dia holes are recommended for parallel conductors on
208/230 v units.
5. Circled numerals in Top View refer to condenser fans by position.
6. If spring isolators are used, a perimeter support channel between the unit
and the isolators is recommended.
7. See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A
and 2B for A-D corner weights.
Fig. 3 Dimensions Unit 38AH094