INSTALLATION 
SELECTION OF MOUNTING POSITION 
1)  The unit should be installed outdoors. 
2)  A place where air will not be stagnant. 
3)  A place where the exhausted air will not be sucked in for 
the second time. 
4)  Allow sufficient space for airflow clearance, wiring, 
refrigerant piping and servicing unit. See Fig. 2. 
5)  Avoid positioning unit in such a manner that water will 
pour directly onto the unit. 
6)  Do not install the unit near a source of heat, steam or 
flammable gas. 
7)  Ducting of the fan inlet or discharge is not permitted. 
 
UNIT MOUNTING 
1)  MOUNTING ON GROUND – Mount on a solid, level 
concrete base. If conditions or local building codes 
require unit to be fastened to base, tie down bolts 
should be used and fastened through slots provided in 
unit’s mounting feet (Fig. 3). Do not install unit directly 
on ground. 
 
2)  MOUNTING ON AND AGAINST THE WALL – the 
bracket is to be locally procured (Fig. 4). 
 
3)  MOUNTING ON ROOF – Mount on a level platform or 
frame. When multiple unit are installed, the air outlet 
side should be opened as shown in Fig. 5. 
 
When installation base is used, secure the required spacing 
as per (Fig. 6). Fabricate the stand so that it will have 
sufficient strength. 
 
 
 
 
REFRIGERANT PIPING 
Size Refrigerant Lines. Consider length of piping required 
between unit and evaporator, amount of liquid lift and 
compressor oil return (Table 4). 
 
Run refrigerant tubes as directly as possible, avoiding 
unnecessary turns and bends. Condensing unit may be 
connected to evaporator sections using field-supplied 
tubing of refrigerant grade, correct size and condition. 
Suspend refrigerant tubes so they do not transmit 
vibration to structure. Also when passing refrigerant 
tubes through walls, seal opening so vibration is not 
transmitted to structure. Leave some slack in refrigerant 
tubes between structure and unit to absorb vibration. 
The longer the piping, the lower the cooling capacity of 
the unit. See table 3. 
 
TABLE 3 – REDUCTION IN CAPACITY VS    
                  INCREASE IN PIPE LENGTH 
 
MODEL
38ASB /
CCAR 5m 10m 15m 20m 25m 30m
240 0% 1.2% 2.0% 2.8% 3.5% 4.5%
360 / 036 0% 1.6% 2.6% 3.6% 4.6% 5.6%
600 / 060 0% 2.8% 4.8% 6.7% 8.7% 10.2%
PIPING LENGTH (ONE WAY)
 
As such the following are the operating limits. Refer to 
Table 4 and fig. 7. 
 
TABLE 4 – VERTICAL AND HORIZONTAL 
                   SEPARATION BETWEEN INDOOR 
                   AND OUTDOOR UNIT 
 
MODEL MAX. MAX.
38ASB / HEIGHT LENGTH MAX. ALLOWABLEMAX. ALLOWABLE
CCARS024~060 H(m) L(m) PRESSURE DROP TEMPERATURE
(kPa)
024 (20)15 25
360 / 036 (20)15 25
600 / 060 (25)15 30
LIQUID LINE
151 5
Note: 1) Values shown are for units operating at 7.2
0
C saturated suction 
              and 35
0
C entering air. 
          2) Values in ( ) indicate a case when the outdoor unit is located at 
              a lower height than the indoor unit. 
 
 
 
 
 
Do not bury section of line set underground. If any section is buried, 
refrigerant may migrate to cooled buried section during extended period of 
unit shutdown. This causes refrigerant slugging and possible compressor 
damage at start-up. 
 
If either refrigerant tubing or indoor coil is exposed to atmospheric 
conditions for longer than 5 minutes, it must be evacuated to 1000 microns 
to eliminate contamination and moisture in the system. 
FIG. 5 ROOF MOUNTING 
FIG. 6 MINIMUM SPACING REQUIREMENT 
FIG. 7 MAXIMUM ALLOWABLE PIPING LENGTH
           AND ELEVATION DIFFERENCE