PIPING CONNECTIONS 
Complete all installation and piping work required for indoor and 
outdoor units. If brazing is required pass nitrogen or other inert gas 
through piping to prevent formation of cooper oxide. Unit contains R-
22 charge, do not open Schreader valve at this time. Leak test field 
piping by pressure method.  
 
 
PIPING INSULATION 
No refrigerant control device is shipped with the unit except 024 
model. It is already installed in matching Fan coil units, check 
carefully the indoor unit. Insulate suction line adequately (Fig. 8) 
 
 
 
 
 
COMPLETE ELECTRICAL CONNECTIONS 
 
 
 
 
 
 
 
POWER ā Unit is factory wired for voltage shown on name plate. 
Provide adequate fused disconnect switch within sign of unit, readily 
accessible, but out of reach children. 
 
Provide for locking switch open (OFF) is advisable to prevent power 
from being turned on w hile unit is being serviced. 
 
Route power wires through opening in unit side panel and connect in 
unit control box (fig. 9). Unit must be grounded. 
 
 
 
 
 
CONTROL CIRCUIT WIRING 
Refer to wiring diagram for field supplied wiring details. 
See Fig. 11 & 12. 
 
Note: - Operation of unit on improper line voltage constitutes 
            abuse and could affect Carrier Warranty. Do not install  
            unit in system where voltage may fluctuate above or below  
            permissible limits. 
 
START-UP 
PRELIMINARY CHECKS: 
1)  Check that all internal wiring connections are tight and all 
barriers, covers and panels are in place. 
2)  Field electrical power source must agree with unit name 
plate rating. 
3)  All service valves must be opened. 
 
START SYTEM 
1.  Check that field disconnect is closed. 
2.  Set room thermostat to below room temperature, and unit 
compressor will start after 3 minutes delay o. 
3.  Check back pressure when compressor runs. Add charge to 
keep back pressure at approximately 448kPa (65 PSIG). 
 
 
 
 
REFRIGERANT CHARGING 
 
 
 
 
 
 
 
 
 
       IMPORTANT 
 
For accurate system performance, charge by superheat method 
as shown in table 5 and 6. 
 
To check and adjust charge, follow the following procedures:- 
 
1)  Operate unit for a minimum of 15 minutes before checking 
charge. 
2)  Measure suction pressure by attaching a gauge to suction 
line service port. 
3)  Measure suction line temperature by attaching a service 
thermometer to unit suction line near suction valve. 
Insulate thermometer for accurate readings. 
4)  Measure outdoor coil air inlet dry-bulb temperature with a 
second thermometer. 
5)  Measure indoor coil air inlet wet-bulb temperature with a 
sling psychrometer. 
6)   Refer to table 5. Find air temperature entering outdoor coil 
& wet-bulb temperature entering indoor coil. At this 
intersection, note the superheat.   
7)  Refer to table 6 . Find superheat temperature and suction 
pressure, note suction line temperature.  
 
FIG. 8 PIPING INSULATION 
THE CONTROL VOLTAGE FROM THE FAN COIL UNIT 
MUST BE OF 230V. DO NOT CONNECT THE POWER 
SUPPLY TO THE SIGNAL 
FIG. 9 POWER WIRES TO THE SIDE OF UNIT 
TO PREVENT PERSONAL INJURY, WEAR SAFETY 
GLASSES AND GLOVES WHEN HANDLING 
REFRIGERANT. DO NOT OVERCHARGED SYSTEM. 
THIS CAN CAUSE COMPRESSOR FLOODING.