11
Condenser only ratings (S.I.) continued
SST — Saturated Temperature Entering Compressor (°C)
TCG — Gross Cooling Capacity (Kw)
KW Total Power (Kw)
SDT — Saturated Temperature Leaving Compressor (°C)
System Design
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wg.
2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature is 125°F (51.7°C).
4. For reliable operation, unit should be level in all horizontal planes.
5. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft (15.24m), indoor coil below = 150 ft
(45.72m).
6. For interconnecting refrigerant tube lengths greater than 50 ft (15.24m), consult Long-Line Application Guideline available from equipment
distributor.
7. Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft (15.24m).
8. If any refrigerant tubing is buried, provide a minimum 6 in. (152mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (912mm) may be buried without further consideration. For buried lines longer than 3 ft (912mm), consult your local
distributor.
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
SST
°C
CONDENSER ENTERING AIR TEMPERATURES °C
20 24 28 32 36 40 44 48 52
38CKX060-91
–2
TCG 15.4 14.9 14.4 13.8 13.3 12.8 12.2 11.7 11.1
KW 3.48 3.78 4.12 4.49 4.88 5.29 5.72 6.17 6.63
SDT 34.6 38.7 42.9 47.0 51.2 55.3 59.3 63.2 67.0
0
TCG 16.4 15.9 15.3 14.8 14.2 13.6 13.1 12.5 11.9
KW 3.56 3.86 4.21 4.58 4.97 5.39 5.83 6.29 6.76
SDT 35.3 39.5 43.6 47.8 51.9 56.0 60.0 64.0 67.9
2
TCG 17.4 16.9 16.3 15.8 15.2 14.5 13.9 13.3 12.7
KW 3.64 3.95 4.30 4.67 5.06 5.49 5.94 6.41 6.89
SDT 36.0 40.2 44.4 48.5 52.6 56.8 60.8 64.8 68.7
4
TCG 18.5 18.0 17.4 16.7 16.1 15.5 14.8 14.2 13.5
KW 3.73 4.04 4.39 4.77 5.16 5.59 6.06 6.54 7.02
SDT 36.8 41.0 45.1 49.3 53.4 57.5 61.6 65.6 69.5
6
TCG 19.7 19.1 18.4 17.8 17.1 16.5 15.8 15.1 14.4
KW 3.83 4.14 4.49 4.87 5.27 5.71 6.18 6.67 7.16
SDT 37.6 41.8 46.0 50.1 54.2 58.3 62.4 66.5 70.4
8
TCG 20.9 20.2 19.6 18.9 18.2 17.5 16.7 16.0 15.2
KW 3.93 4.25 4.60 4.98 5.39 5.82 6.30 6.80 7.31
SDT 38.5 42.6 46.8 50.9 55.1 59.2 63.3 67.3 71.3
10
TCG 22.1 21.4 20.7 20.0 19.3 18.5 17.7 16.9 16.1
KW 4.04 4.36 4.72 5.10 5.51 5.95 6.43 6.93 7.46
SDT 39.3 43.5 47.7 51.8 55.9 60.0 64.1 68.1 72.2