EasyManua.ls Logo

Carrier 38GLP---G - Dimensions and Weight; Connections

Carrier 38GLP---G
16 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38GLP---G / 38GLP---G9
GB - 2
Dimensions and weight
Mod. 38GLP 18 - 24 Mod. 38GLP 28 - 36
Mod.
38GLP
18 24 28 36 48 60
A mm 800 800 800 800 800 800
B mm 590 590 803 803 1264 1264
C mm 300 300 300 300 300 300
D mm 508 508 508 508 508 508
E mm 146 146 146 146 146 146
F mm 330 330 330 330 330 330
kg 45 51 65 65 92 94
Mod. 38GLP 48 - 60
3
1
2
Outdoor unit
Indoor unit
Height difference
Connessioni
Model
18 24 28 36 48 60
Max. height difference
30 m 40 m 40 m 50 m 50 m 50 m
Max. pipe length
10 m 15 m 25 m 30 m 30 m 30 m
Table II: Connections
3
1
2
Model Pipe diameter Pipe diameter
Gas Liquid Gas Liquid
mm inches
18
12.70 6.35 1/2" 1/4"
24
28 15.87 6.35 5/8" 1/4"
36
48 19.05 9.52 3/4" 3/8"
60
All fittings are flare type.
Use only refrigeration grade pipes, (Cu DHP type according to ISO 1337),
seamless, degreased, deoxidized and suitable for operating pressures of at
least 4200 kPa and with a burst pressure of 20700 kPa.
Under no circumstances must sanitary type copper pipe be used.
EED
B
C
F
A
EED
B
C
F
A
EED
B
C
F
A

Related product manuals