13
AIR THROW DATA
Model Number
Approximate Air Throw ft. (m)
Low Medium High Turbo
4 0 G X M 0 0 9 --- --- --- 3 20 (6.1) 22 (6.7) 25 (7.6) 28 (8.5)
4 0 G X M 0 1 2 --- --- --- 3 22 (6.7) 25 (7.6) 27 (8.2) 31 (9.4)
4 0 G X M 0 1 8 --- --- --- 3 23 (7.0) 29 (8.8) 32 (9.8) 35 ( 10.7)
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBA Sound Pressure dBA
3 8 G X M 2 1 8 --- --- --- 3
(cool/heat)
68/68 57/57
3 8 G X M 2 2 4 --- --- --- 3
(cool/heat)
68/68 57/57
3 8 G X M 4 3 0 --- --- --- 3
(cool/heat)
70/70 59/59
Indoor Units
Model Number
Low Medium High Turbo
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
Sound
Power
dBA
Sound
Pressure
dBA
4 0 G X M 0 0 9 --- --- --- 3
(cool/heat)
42.0 31.0 47.0 36.0 51.0 40.0 54.0 43.0
4 0 G X M 0 1 2 --- --- --- 3
(cool/heat)
44.0 33.0 46.0 35.0 48.0 47.0 53.0 42.0
4 0 G X M 0 1 8 --- --- --- 3
(cool/heat)
52.0 41.0 55.0 44.0 57.0 46.0 60.0 49.0
NOTES:
1. Sound power ratings are per AHRI 270 and AHRI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
ELECTRICAL DATA
UNIT
SIZE
SYSTEM
VOLTAGE
OPERATING
VOLTAGE*
COMPRESSOR
OUTDOOR FAN INDOOR FAN{
MCA
MAX
FUSE/CB
AMP
V O L T --- P H --- H Z MAX/MIN RLA LRA FLA HP W VOLTS FLA HP W
18 K
208/230---1---60 253/187
3.8 41
0.65
0.082 60 208/230---1 ---60 0.26 0.19 14
14 20
24 K
8.2 34
20 30
30 K 0.68 24 40
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ Indoor fa n powered f rom outdoor unit.
LEGEND
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d R o t o r A m p s
MCA --- Minimum Circuit Amps
RLA --- RatedLoadAmps
38/40GXM