DIAGNOSTIC GUIDES
Table 14—Diagnostic Guides Indoor Units
OPERATION LAMP TIMER LAMP DISPLAY LED STATUS
1 time X E0 Indoor unit EEPROM parameter error
2 times X E1 Communication malfunction between indoor and outdoor units
4 times X E3 Indoor fan speed malfunction
5 times X E4 Indoor room temperature sensor (T1 ) malfunction
6 times X E5 Evaporator coil temperature sensor (T2) malfunction
7 times X EC Refrigerant leakage detection
8 times X EE Water-level alarm malfunction
1 time O F0 Current overload protection
2 times O F1 Outdoor ambient temperature sensor (T4 ) malfunction
3 times O F2 Condenser coil temperature sensor (T3) malfunction
4 times O F3 Compressor discharge temperature sensor (T5) malfunction
5 times O F4 Outdoor unit EEPROM parameter error
6 times O F5 Outdoor fan speed malfunction
7 times O F6 Indoor coil outlet pipe sensor(Located on outdoor unit low pressure valve)
8 times O F7 Communication malfunction between the cassette optional lift panel and the unit
9 times O F8 Cassette optional lift panel malfunction
10 times O F9 Cassette optional lift panel not closed
1 time P0 Inverter module (IPM) malfunction
2 times P1 Over-voltage or under-voltage protection
3 times P2 Compressor top high temperature protection (OLP)
4 times P3 Low ambient temperature cut off in heating
5 times P4 Compressor drive malfunction
6 times P5 Indoor units mode conflict
7 times P6 Low pressure protection
8 times P7 Outdoor IPM temperature sensor error