ELECTRICAL DATA
UNIT SIZE
OPER.
VOLTAGE
MAX / MIN
COMPRESSOR OUTDOOR F AN INDOOR FAN
MCA
MAX FUSE
CB AMP
V --- P H --- H Z RLA LRA V --- P H --- H Z FLA HP W V --- P H --- H Z FLA HP W
9K
127 / 104 115--- 1 --- 6 0 5.30 10 11 5 --- 1 --- 6 0 0.7 0.31 23 11 5 --- 1 --- 6 0 0.3 0.020 15 19 30
12K
12K
253 / 187 2 0 8 --- 2 3 0 --- 1 --- 6 0
5.30 10
2 0 8 --- 2 3 0 --- 1 --- 6 0
0.3 0.33 24
2 0 8 --- 2 3 0 --- 1 --- 6 0
0.2 0.027 20 10 15
017K (HP) /
018K (AC)
3.95 14 0.6 0.68 50 0.3 0.038 28 14 20
22K 9.70 17 0.6 0.72 53 0.4 0.061 45 16 25
CONNECTION DIAGRAMS
S
L
N
115-1-60
       Main 
Power Supply
115-1-60
1(L)
2(N)
S
L
N
Power to 
Indoor Unit
CONNECTING CABLE
OUTDOOR TO INDOOR
GND
Indoor Unit
Power  Supply
Ground
Indoor 
Signal
High
Voltage
115-1-60
           115-1-60
FIELD POWER SUPPLY
GND
Indoor 
Signal
High
Voltage
9K and 12K 115V INDOOR UNIT 9K and 12K 115V OUTDOOR UNIT
S
L1
L2
208-230-1-60
       Main 
Power Supply
208-230-1-60
L1
L2
S
L1
L2
CONNECTING CABLE
OUTDOOR TO INDOOR
Indoor Unit
Power  Supply
208-230-1-60
Indoor 
Signal
High
Voltage
GND
Ground
Power  to
Indoor Unit
Indoor 
Signal
High
Voltage
          208-230-1-60
FIELD POWER SUPPLY
GND
12K to 22K 208-230V INDOOR UNIT
12K to 22K 208-230V OUTDOOR UNIT
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
Fig. 12 --- Connection Diagrams