STARTUP
Test Operation
Perform test operation after completing gas leak and electrical
safety check. See the indoor unit installation instructions and
owner’s manual for additional start up information.
SYSTEM CHECKS
1. Conceal the tubing where possible.
2. Ensure the drain tube slopes downward along its entire
length.
3. Ensure all tubing and connections are properly insulated.
4. Fasten tubes to the outside wall, when possible.
5. Seal the hole through which the cables and tubing pass.
OUTDOOR UNIT
1. Are there unusual noises or vibrations during operation?
Explain the Following Items To Customer (with the aid of the
Owner’s Manual):
2. Explain care and maintenance.
3. Present the Owners Manual and installation instructions to
customer.
OUTDOOR UNIT DIAGNOSTIC GUIDES
This unit has onboard diagnostics. Error codes are displayed on the wired remote controller and the outdoor unit microprocessor board with
colored LED lights. Table 14 explains the error codes on both.
Table 14—Outdoor Unit Error Display
DISPLAY LED STATUS IDU Error IDU Error
E0 Outdoor EEPROM malfunction F4 E6
E2 Communication malfunction between indoor and outdoor units E1 E2
E3 Communication malfunction between IPM board and outdoor main board —— ——
E4 Open or short circuit of outdoor temperature sensor (T3T4T5T2B) F2 E6
E5 Voltage protection P1 P0
E6 PFC module protection —— ——
E8 Outdoor fan speed has been out of control (Only for DC fan motor models) F5 ——
E9 Wrong wiring connection of 24K indoor unit —— ——
F1 No A Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F2 No B Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F3 No C Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F4 No D Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F5 No E Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
F6 No F Indoor unit coil outlet temp. sensor or connector of sensor is defective —— ——
P0 Temperature protection of compressor top P2 P3(P1)
P1 High pressure protection —— ——
P2 Low pressure protection —— ——
P3 Current protection of compressor —— ——(P2)
P4 Temperature protection of compressor discharge —— ——
P5 High temperature protection of condenser —— ——
P6 IPM module protection P0 E5