38MGR-04SM                              Specifications subject to change without notice.                                  29
End Defrosting Action
If any one of following items is satisfied, defrosting stops and the 
machine enters the normal Heating mode.
1. T3 > TempQuitDefrost_ADD °C
2. The defrosting time achieves 10 minutes
3. Turn to other modes or OFF
Outdoor Fan Control
Cooling Mode
Under normal  operating  conditions,  the  system  chooses the  running
fan speed according to the ambient temperature.
Fig. 37 — Cooling Mode
When low ambient cooling is in effect:
The outdoor fan speed controls logic (low ambient cooling).
When T4 < 59.(15°C) and T3 < 86.(30°C), the unit enters into the
low ambient cooling mode. The outdoor fan chooses a speed 
according to T3.
When T3≥100.4.(38°C) or when T4≥68.(20°C), the outdoor fan 
chooses a speed according to T4 again.
Fig. 38 — Cooling Mode
Fig. 39 — Cooling Mode
Heating Mode
Under normal operating conditions, the system chooses a running fan
speed according to the ambient temperature.
Fig. 40 — Heating Mode
Electronic Expansion Valve (EXV) Control
1. EXV is fully closed when power is turned on. The EXV will 
standby with the 350P open and then opens to the target angle after 
the compressor starts.
2. EXV  closes with  -  160P when the compressor stops. Then  EXV
will standby with the 350P open and then opens to the target angle
after the compressor starts.
3. The action priority of the EXVs is A-B-C-D-E.
4. Compressor and the outdoor fan start operation only after the EXV
is initialized.
Cooling Mode
The initial open angle of EXV is dependent on indoor model size, 
adjustment range is 100-400p. When the unit starts to work for three 
minutes, the outdoor unit receives the indoor units’ (of capacity 
demand) T2B information and calculates their average. 
After comparing each indoor T2B with the average. the outdoor gives 
the following modification commands: if the T2B>average, the 
relevant valve needs more 16p open. If the T2B = average, the 
relevant valve’s open range remains. If the T2B<average, the relevant 
valve needs more 16p close. This modification will be carried out 
every two minutes.
38
Exit low ambient cooling
mode
,
 run with high fan
for 1 minute
Low
Increase fan speed
Keep current fan speed
Decrease fan speed
Fan stop