Table 10 —Data Table
MODEL NAME 38VMA168RDS6-1 38VMA192RDS6-1
Power Source V-Ph-Hz 460-3-60
Capacity Cooling*1 Btu/h 168,000 192,000
Capacity Heating*1 Btu/h 188,000 215,000
Operating Range
Cooling
Indoor WB°F 59~75
Outdoor DB°F 5~125
Operating Range
Heating
Indoor DB°F 54~86
Outdoor WB°F -13~64
Electrical Supply
MCA A 35
Recommended Fuse Size A 40
Compressor
Type x Quantity INVERTER-driven Scroll Hermetic x 2
Crankcase W 30 x 4
Fan
Type x Quantity Propeller Fan x 2
Air flow rate CFM 10,100 11,300
Max. External static pressure *2 0.24 in. WG
Fan Motor
Type Brushless DC MOTOR
Output W 260 + 260 340 + 340
Heat Exchanger
Inner Groove Copper Tube and
Hydrophilic Aluminum fin
Condenser Coil
Coil Qty. 2
FT
2
26
Rows 3
FPI 17
Refrigerant
Type R410A
Factory charge lbs. 44.2
Dimensions
H (in.) 64-3/8
W (in.) 78-3/8
D (in.) 31-1/8
Net Weight lbs 1,137
Sound pressure level*3 dBA 63.3 64.9
Protective devices
High Pressure Protection High pressure switch at 580psi
Inverter circuit (Comp. / Fan) Overheat and Overcurrent protection
Piping Connections
Low Pressure in. 1-1/8
High Pressure in. 7/8
Indoor unit
Total capacity*4 50%-150%
Quantity (MAX) 34 39
REMARKS:
*1 Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230 Standard.
Cooling: Indoor 80°F db/67°F wb; Outdoor 95°F db
Heating: Indoor 70°F db; Outdoor 47°F db/43°F wb
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*2 ESP can vary by menu settings from 0in.WG (Default), 0.08 in. WG, 0.16 in. WG to 0.24 in. WG.
*3 These values, measured in anechoic chamber, are normally somewhat higher as a result of actual ambient conditions.
*4 See “Combination Ratio Restrictions” on page 18.