37
CONTROL WIRING
Use  2-Core  stranded  shielded  communication  wire.  Wiring  length  limitations  must  be  observed  to  avoid  any
communication interference.
Table 29 —Wiring Length Limitation
Fig. 19 —Controls Wiring
Max. length to Outdoor L1+L2,L5 ≤3937ft [1,200m] AWG 18
Max. total length to Indoor units L3, L3+L4 ≤3937ft [1,200m] AWG 18
Max. length from controller to indoor units L6+L7+ L8+ L9, L10+L11 ≤820ft [250m] AWG 18