7
Table 5 —Data Table
MODEL NAME 38VMA240RDL5-1 38VMA264RDS5-1
Power Source V-Ph-Hz 208/230-3-60
Capacity Cooling*1 Btu/h 240,000 264,000
Capacity Heating*1 Btu/h 270,000 295,000
Operating Range
Cooling
Indoor WB°F 59~75
Outdoor DB°F 5~125
Operating Range
Heating
Indoor DB°F 54~86
Outdoor WB°F -13~64
Electrical Supply
MCA A 101 104
Recommended Fuse Size A 110
Compressor
Type x Quantity INVERTER-driven Scroll Hermetic x 3
Crankcase W 30 x 6
Fan
Type x Quantity Propeller Fan x 4
Air flow rate CFM 14,500 15,500
Max. External static pressure *2 0.24 in. WG
Fan Motor
Type Brushless DC MOTOR
Output W 225 x 4 265 x 4
Heat Exchanger Inner Groove Copper Tube and Hydrophilic Aluminum fin
Condenser Coil
Coil Qty.
2
FT
2
28-3/4
Rows
3
FPI
16
Refrigerant
Type R410A
Factory charge lbs. 77.2
Dimensions
H (in.) 64-3/8
W (in.) 105-7/8
D (in.) 31-1/8
Net Weight lbs 1,627
Sound pressure level *3 dBA 63.9 64.8
Protective devices
High Pressure Protection High pressure switch at 580psi
Inverter circuit (Comp. / Fan) Overheat and Overcurrent protection
Piping Connections
Low Pressure in. 1-3/8
High Pressure in. 1-1/8
Indoor unit
Total capacity *4 50%-150%
Quantity (MAX) 49 54
REMARKS:
*1 Rated per AHRI (Air-Conditioning, Heating and Refrigeration Institute) 1230 Standard.
Cooling: Indoor 80°F db/67°F wb; Outdoor 95°F db
Heating: Indoor 70°F db; Outdoor 47°F db/43°F wb
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be
referred to the Installation Manual.
*2 ESP can vary by menu settings from 0in.WG (Default), 0.08 in. WG, 0.16 in. WG to 0.24 in. WG.
*3 These values, measured in anechoic chamber, are normally somewhat higher as a result of actual ambient conditions.
*4 See “Combination Ratio Restrictions” on page 18.