46
P4: DISCHARGE TEMPERATURE PROTECTION
DEFINITION
Discharge temperature protection is activated when discharge temperature is higher than 230°F.
System will restart once the discharge temperature (T5) is below 190°F.
POSSIBLE CAUSES
Stop valve is closed
Improper power supply
Insufficient refrigerant in the system
Damaged valve or filter resulting in large pressure ratio
Damaged main board
A210288
Fig. 53 —P4 Troubleshooting Chart
*B Refer to resistance temperature sensor in Appendix.