47
P5: CONDENSER TEMPERATURE PROTECTION
DEFINITION
Condenser temperature protection is activated when condenser temperature is higher than 144°F.
System will restart once the condensing temperature (T3) is below 126°F.
POSSIBLE CAUSES
Stop valve is closed
Improper airflow
Temperature sensor error
Other heat resources around T3
Damaged main board
A210289
Fig. 54 —P5 Troubleshooting Chart
*A Refer to resistance of temperature sensor in Appendix.