48
P8: FAN SPEED EXCEEDS TARGET FAN MOTOR ROTATION FOR FIVE SECONDS OR MORE
DEFINITION
When fan speed exceeds minimum target fan motor rotation (500 RPM) for five seconds or more, protection is activated.
System will restart once the fan speed is < 400 RPM.
POSSIBLE CAUSES
Fan speed exceeds the target fan motor rotation due to excessive wind.
PE: HIGH INDOOR COIL TEMPERATURE (T2A) PROTECTION
DEFINITION
High indoor coil temperature (T2A) protection is activated when coil temperature is higher than 144°F.
The unit will restart once the coil temperature (T2A) is below 109.4°F.
POSSIBLE CAUSES
Air filter or indoor coil are dirty
Temperature sensor (T2A) error
Other heat resources around T2A
Damaged main board of indoor unit
A210290
Fig. 55 —P8 Troubleshooting Chart
*A Refer to resistance of temperature sensor in Appendix.