PP: LIQUID SLUGGING PROTECTION
DEFINITION
The discharge superheat of compressor is less than 5.4°F for 50 minutes.
POSSIBLE CAUSES
Defective discharge temperature sensor
Damaged main board
Excess refrigerant charge
Improper valve function of IDU or ODU
Defective indoor unit fan
A210291
Fig. 56 —PP Troubleshooting Chart