EasyManua.ls Logo

Carrier 40MAHBQ24XA3 User Manual

Carrier 40MAHBQ24XA3
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Specifications subject to change without notice.
TABLE of CONTENTS
PAGE
INTRODUCTION............................................................................ 1
MODEL / SERIAL NUMBER NOMENCLATURES .................... 2
SPECIFICATIONS .......................................................................... 3
COMPATIBILITY........................................................................... 3
DIMENSIONS ................................................................................. 4
CLEARANCES................................................................................ 4
ELECTRICAL DATA ..................................................................... 5
WIRING........................................................................................... 5
CONNECTION DIAGRAMS ......................................................... 6
WIRING DIAGRAM....................................................................... 7
REFRIGERATION CYCLE DIAGRAM........................................ 8
REFRIGERANT LINES .................................................................. 8
FAN AND MOTOR SPECIFICATIONS........................................ 9
SYSTEM EVACUATION AND CHARGING ............................... 10
TROUBLESHOOTING................................................................... 15
INDOOR UNIT DIAGNOSTIC GUIDE......................................... 16
DIAGNOSIS AND SOLUTION...................................................... 17
APPENDICIES ................................................................................ 34
DISASSEMBLY INSTRUCTIONS ................................................ 37
Installing, starting up, and servicing air conditioning equipment can
be hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.). Only trained,
qualified installers and service mechanics should install, start-up, and
service this equipment. Untrained personnel can perform basic
maintenance functions such as coil cleaning. All other operations
should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature
and on tags, stickers, and labels attached to the equipment. Follow all
safety codes. Wear safety glasses and work gloves. Keep a quenching
cloth and fire extinguisher nearby when brazing. Use care in handling,
rigging, and setting bulky equipment.
Read this manual thoroughly and follow all warnings or cautions
included in the literature and attached to the unit. Consult local
building codes and National Electrical Code (NEC) for special
requirements. Recognize safety information. This is the safety-alert
symbol . When you see this symbol on the unit and in instructions
or manuals, be alert to the potential for personal injury. Understand
these signal words: DANGER, WARNING, and CAUTION.
These words are used with the safety-alert symbol. DANGER
identifies the most serious hazards which will result in severe personal
injury or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which may result in minor personal injury or product and
property damage. NOTE is used to highlight suggestions which will
result in enhanced installation, reliability, or operation.
INTRODUCTION
This service manual provides the necessary information to service,
repair, and maintain the 40MAHB family of heat pumps. This manual
has an appendix (see “APPENDICIES” on page 34) with data
required to perform troubleshooting. Use the “TABLE of
CONTENTS”on page 1 to locate a desired topic.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing the system, the
main electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch. Lock
out and tag switch (es) with a suitable warning label.
WAR N I N G
EXPLOSION HAZARD
Failure to follow this warning could result
in death, serious personal injury, and/or
property damage. Never use air or gases
containing oxygen for leak testing or
operating refrigerant compressors.
Pressurized mixtures of air or gases
containing oxygen can lead to an explosion.
WAR N I N G
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in
the ground. If any section of pipe is buried, there must be a 6
in. (152 mm) vertical rise to the valve connections on the
outdoor units. If more than the recommended length is buried,
refrigerant may migrate to the cooler buried section during
extended periods of a system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start-up.
CAUTION
Service Manual
40MAHB
High Wall Ductless System
Sizes 06 to 36

Other manuals for Carrier 40MAHBQ24XA3

Question and Answer IconNeed help?

Do you have a question about the Carrier 40MAHBQ24XA3 and is the answer not in the manual?

Carrier 40MAHBQ24XA3 Specifications

General IconGeneral
BrandCarrier
Model40MAHBQ24XA3
CategoryAir Conditioner
LanguageEnglish

Summary

Model and Serial Number Nomenclature

Specifications

Compatibility

Electrical Data and Wiring

Connection Diagrams

Wiring Diagram

Refrigeration System Overview

Fan and Motor Specifications

System Evacuation and Charging

Deep Vacuum Method

Explains the deep vacuum method for system evacuation.

Triple Evacuation Method

Details the steps for the triple evacuation method.

Unit Protection Functions

Special Operation Modes

Troubleshooting Safety Precautions

Indoor Unit Diagnostic Guide

Diagnosis and Solution

EEPROM Parameter Error Diagnosis (E0/F4)

Troubleshooting for EEPROM parameter errors.

Communication Error Diagnosis (E1)

Troubleshooting indoor/outdoor unit communication errors.

Zero Crossing Detection Error Diagnosis (E2)

Troubleshooting zero crossing detection errors.

Fan Speed Control Error Diagnosis (E3/F5)

Troubleshooting fan speed control errors.

Temperature Sensor Error Diagnosis (E4/E5/F1/F2/F3)

Troubleshooting temperature sensor open circuit or short circuit.

Refrigerant Leakage Detection Diagnosis (EC)

Troubleshooting refrigerant leakage detection codes.

Overload Current Protection Diagnosis (F0)

Troubleshooting overload current protection errors.

Main Parts Check

IPM Continuity Check

Disassembly Instructions

Related product manuals