14
REFRIGERANT LINES
General refrigerant line sizing:
1 The outdoor units are shipped with a full charge of R410A
refrigerant. All charges, line sizing, and capacities are based
on runs of 25 ft (7.6 m). For runs over 25 ft (7.6 m), refer to
the Residential Long Line Guide.
2 Minimum refrigerant line length between the indoor and
outdoor units is 10 ft. (3 m).
3 Refri gerant line s should not be buried in the ground. If it is
nece ssary to bury the li nes , not more tha n 36--in (914 mm)
should be buri ed. Provide a minimum 6--in (152 mm) vertic al
rise to the se rvice valves to prevent refrigera nt migr at i on.
4 Both lines must be insulated. Use a minimum of 1/2--in.
(12.7 mm) thick insulation. Closed--cell insulation is
recommended in all long --line applications.
5 Specia l cons ide r at i on should be given to is olating
interconnecting tubing from the building structure. Isolate the
tubing so that vibrat i on or nois e does not transmi t into the
structure.
IMPORTANT: Both refrigerant lines must be insulated
separately.
S The following maximum lengths are allowed:
Table 12 – Maximum Refrigerant Line Lengths
Unit
Size
Max Line
Length* ft(m)
Max Elevation
(ID over OD) ft( m)
Max Elevation
(OD over ID) ft (m)
18K 250 (76.2) 65 (19.8) 200 (61)
24K 250 (76.2) 65 (19.8) 200 (61)
30K 250 (76.2) 65 (19.8) 200 (61)
36K 250 (76.2) 65 (19.8) 200 (61)
Note: For lengths greater than 25 ft. (7.6 m), refer to the Residential
Long Line Guide.
*Maximum actual length not to exceed 200 ft. (61 m). Total equivalent
length accounts for losses due to elbows or fitting. See the Long Line
Guideline for details.
S The following are the piping sizes.
Table13–PipeSizes
Pipe Sizes (in)
Unit Size Mix Phase -- in Vapo r - - in
18K 3/8 5/8
24K 3/8 3/4
30K 3/8 3/4
36K 3/8 7/8
Note: Both lines need to be insulated using at least 1/2 inch closed
foam insulation.
Refrigerant Charge
Table 14 – Charge Requirements
System
Ty p e
Nominal
Capacity
Outdoor Unit Indoor Unit
Charge to
Sub--cooling Delta
from Rating Plate
Va lu e
Cooling
Only
018 24AHA418A003 124ANS018000 40MKCB18B----3 12
022 24AHA424A003 124ANS024000 40MKCB22B----3 12
028 24AHA430A003 124ANS030000 40MKCB28B----3 12
032 24AHA436A003/5/6 124ANS036000 40MKCB32B----3 8
Heat
Pump
024 25HHA424A003 224ANS024000 40MKQB24B---- 3 14
028 25HHA430A003 224ANS030000 40MKQB28B---- 3 11
The above additional charge is required amount for line lengths up to
25 ft (7.6 m). F or line lengths exceeding 25 ft. (7.6 m), additional
charge will be required. Refer to the Residential Long Line Guide.
Metering Device
The metering device(s) for these systems is a type B accurator. The
cooling accurator is installed with the indoor unit, while the
heating accurator is installed with the outdoor unit. One Accurator
is required for the cooling only system and two are required for the
heat pump systems. Refer to Table 15 for the accurator size.
Table 15 – Accurator Sizes
System Size
Cooling Only Heat Pumps
40MKC**B 40MKQ**B 25HHA4/224ANS
018 0.046” -- --
022, 024 0.052” 0.052” 0.049”
028 0.059” 0.057” 0.055”
032 0.065” -- --
SYSTEM EVACUATI ON AND
CHARGING
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Never use the system compressor as a vacuum pump.
CAUTION
!
Refrigerant tubes and indoor coil should be evacuated using the
recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used if the procedure outlined
below is followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM AND CHARGE
Using Vacuum Pump
1 Completely tighten flare nuts A, B, C, D, connect manifold
gage charge hose to a charge port of the low side service
valve (see Fig. 16).
2 Connect charge hose to vacuum pump.
3 Fully open the low side of manifold gage (see Fig. 17).
4 Start the vacuum pump.
5 Evacuate using either deep vacuum or triple evacuation
method.
6 After evacuation is complete, fully close the low side of
manifold gage and stop operation of vacuum pump.
7 The fact or y charge contained in the outdoor uni t i s good for up
to 25 ft. (8 m) of line length. For re frige r ant lines longer than
25 ft. (8 m), add cha rge, up to the maximum allow able le ngth,
as specified in the residential Long Line Appli cat i on Guide.
8 Disconnect charge hose from charge connection of the low
side service valve.
9 Fully open service valves B and A.
10 Securely tighten caps of service valves.
Outdoor Unit
Indoor Uni
Refrigerant
Service Valve
Low Side
High Side
A
B
C
D
A07360
Fig. 16 – Service Valve
Manifold Gage
500 microns
Low side valve
High side valve
Charge hose
Charge hose
Vacuum pump
Low side valve
A07361
Fig. 17 – Manifold