28
PERFORMANCE DATA (CONT.)
INSTANTANEOUS AND INTEG. HEATING RATINGS
40QAQ024 / 38QRR018
Air
Te m p e r a t ur e
Entering
Indoor Unit
°F(°C)
Indoor
Airflow
(CFM)
L --- M --- H
Item
Air Temperature Entering Outdoor Coil ° F C)
17 ( --- 8.3) 27 ( --- 2.8) 37 (2.8) 47 (8.3) 57 (13.9)
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
Instant.
Rating
Integ.
Rating
55
(12.8)
320
Cap 9.67 8.81 11.81 10.49 13.85 12.60 17.07 17.07 17.69 17.69
kW 1.17 1.31 1.45 1.58 1.63
400
Cap 9.92 9.04 12.10 10.75 14.17 12.89 17.39 17.39 18.01 18.01
kW 1.11 1.22 1.33 1.44 1.45
480
Cap 10.01 9.12 12.25 10.88 14.41 13.11 17.84 17.84 18.46 18.46
kW 1.06 1.11 1.16 1.20 1.25
60
(15.6)
320
Cap 9.56 8.72 11.84 10.52 13.67 12.44 16.82 16.82 17.56 17.56
kW 1.22 1.29 1.37 1.44 1.49
400
Cap 9.74 8.88 11.99 10.65 14.00 12.74 17.22 17.22 17.95 17.95
kW 1.16 1.22 1.28 1.33 1.38
480
Cap 9.84 8.97 12.06 10.71 14.14 12.87 17.53 17.53 17.99 17.99
kW 1.12 1.17 1.21 1.26 1.30
65
(18.3)
320
Cap 9.35 8.53 11.67 10.37 13.63 12.41 16.53 16.53 17.26 17.26
kW 1.27 1.37 1.47 1.56 1.56
400
Cap 9.56 8.72 11.83 10.50 13.85 12.60 16.98 16.98 17.63 17.63
kW 1.22 1.28 1.34 1.41 1.45
480
Cap 9.68 8.83 11.92 10.58 14.09 12.82 17.26 17.26 17.70 17.70
kW 1.18 1.23 1.28 1.33 1.36
70
(21.1)
320
Cap 9.15 8.35 11.45 10.17 13.38 12.18 16.45 16.45 16.94 16.94
kW 1.33 1.41 1.48 1.55 1.65
400
Cap 9.37 8.55 11.70 10.39 13.66 12.43 16.70 16.70 17.50 17.50
kW 1.28 1.34 1.41 1.48 1.52
480
Cap 9.50 8.66 11.84 10.52 13.88 12.63 17.00 17.00 17.70 17.70
kW 1.24 1.29 1.35 1.40 1.44
75
(23.9)
320
Cap 8.95 8.66 11.45 10.17 13.04 8.66 15.69 15.69 16.60 16.60
kW 1.40 1.51 1.62 1.72 1.75
400
Cap 9.15 8.89 11.66 10.35 13.44 8.89 16.47 16.47 17.00 17.00
kW 1.34 1.42 1.50 1.57 1.64
480
Cap 9.28 8.46 11.66 10.35 13.55 12.33 16.76 16.76 17.11 17.11
kW 1.30 1.36 1.41 1.46 1.56
80
(26.7)
320
Cap 8.71 7.94 11.21 9.96 13.07 11.90 15.32 15.32 15.91 15.91
kW 1.46 1.54 1.62 1.70 1.97
400
Cap 8.91 8.13 11.45 10.17 13.20 12.01 15.45 15.45 16.37 16.37
kW 1.41 1.47 1.53 1.59 1.96
480
Cap 9.09 8.66 11.59 10.30 13.40 12.20 15.65 15.65 16.57 16.57
kW 1.36 1.43 1.51 1.58 1.76
Rating Condition.
Not recommended for long--- term operation
Cap --- Heating C a pacity (1000 Btuh), includes indoor fan motor heat.
kW --- Total power input. Includes compressor motor power input, outdoor fan motor power input, and indoor fan motor power input.
NOTE: Integ. Capacity is maximum (instantaneous ) capacity less the effect of frost on the outdoor coil and the heat to defrost it.
40QAC/38HDR -- 40QAQ/38QR