15.3.5 Inverter module protection 
The Inverter module has a protection function 
about current, voltage and temperature. If these 
protections  happen,  the  corresponding  code 
will display on indoor unit and the unit will stop 
working. 
15.3.6 Indoor fan delayed open function 
When the unit starts up, the louver will be active 
immediately  and  the  indoor fan  will  open  10s 
later. 
If the unit runs in heating mode, the indoor fan 
will  be  also  controlled  by  anti-cold  wind 
function. 
15.3.7 Compressor preheating functions 
Preheating permitting condition: 
If T4<3℃(37.4°F) and  the  machine  connects 
to power supply newly within 5 seconds or if T4
<3℃(37.4°F) and compressor has stopped for 
over 3 hours, the compressor heating cable will 
work. 
Preheating mode: 
A  weak  current  flow  through  the  coil  of 
compressor  from  the  wiring  terminal  of  the 
compressor,  then  the  compressor  is  heated 
without operation. 
Preheating release condition: 
If  T4≥5 ℃ (41°F)  or  the  compressor  starts 
running, the preheating function will stop. 
15.3.9  Condenser  high  temperature  T3 
protection 
---55°C(131°F)<T3<60°C(140°F),  the 
compressor  frequency  will  decrease  to  the 
lower  level  until  to  F1  and  then  runs  at  F1.If 
T3<54°C(129.2°F),  the  compressor  will  keep 
running at the current frequency. 
---T3<52°C(125.6°F),  the  compressor  will  not 
limit  the  frequency  and  resume  to  the  former 
frequency. 
---T3>60°C(140°F)  for  5  seconds,  the 
compressor will stop until T3<52°C(125.6°F). 
15.3.10  Evaporator  low  temperature  T2 
protection 
---T2<0°C(32°F), the compressor will stop and 
restart when T2≧5°C(41°F). 
---0°C(32°F)≦T2<4°C(39.2°F), the compressor 
frequency will be limited and decreased to the 
lower level 
---4°C(39.2°F)≤T2≤7°C(44.6°F),  the 
compressor will keep the current frequency. 
---T2>7°C(44.6°F),  the  compressor  frequency 
will not be limited. 
 
15.4 Operation Modes and 
Functions 
15.4.1 Fan mode 
(1) Outdoor fan and compressor stop. 
(2)  Temperature  setting  function  is  disabled, 
and no setting temperature is displayed. 
(3) Indoor fan can be set to high/med/low/auto. 
(4)  The  louver  operates  same  as  in  cooling 
mode. 
(5) Auto fan: 
a
b
c
d
6.0°C(42.8°F)
T1-24°C(75.2°F)
e
H
(H-L)*0.75+L
(H-L)*0.5+L
(H-L)*0.25+L
L
5.0°C(41.0°F)
4.0°C(39.2°F)
2.5°C(36.5°F)
1.0°C(33.8°F)
15.4.2 Cooling Mode 
15.4.2.1 Outdoor fan running rules 
T4
A DC_FAN_HI_SPD_ADD
B DC_FAN_MID_SPD_ADD
C DC_FAN_MIN_SPD_ADD
D DC_FAN_SLOW_SPD_ADD
E DC_FAN_SSLOW_SPD_ADD
 
15.4.2.2 Indoor fan running rules 
In  cooling  mode,  indoor fan  runs all  the  time 
and  the  speed  can  be  selected  as  high, 
medium, low and auto.