Table3-- ElectricHeaterDatafor UnitswithECM(cont)
UNiT
40UV, UH150
(at 1500 Cfm)
HP
1/2
NOMINAL
V/PIdHz
208/1/60
240/1/60
277/1/60
208/3/60
240/3/60
460/3/60
NUMBER
OF
ELEMENTS
3
4
5
6*
3
4
5*
6
3
4
5
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
DX -- Direct Expansion
FLA -- Full LoadAmps
LAT -- Leaving-Air Temperature at 70 F Entering-Air
Temperature
FLA
46,7
61.1
75.6
90.0
53.3
70.0
86.6
46.2
60.7
75.1
28.3
42.8
53.4
53.4
32.2
48.9
61,1
51,1
15,6
24.0
30.1
30,1
LAT
(F)
89
96
102
108
96
104
113
96
104
113
89
95
102
108
96
104
113
121
96
104
113
121
MCA
58.3
76.4
94.4
112.5
66.6
87.5
108.3
57.8
75.8
93,9
35.4
53.5
66.7
66.7
40.3
61.1
76.4
76.4
19.5
30.0
37.6
37.6
TOTAL
MOCP CAPACITY
(kW)
60 9.0
80 12.0
100 15.0
125 18.0
70 12.0
90 16.0
110 20.0
60 12.0
80 16,0
100 20.0
40 9.0
60 12.0
70 15.0
70 18.0
45 12.0
70 16.0
80 20.0
80 24.0
20 12.0
30 16.0
40 20,0
40 24.0
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse Size
or CircuitBreaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm,
2. Water and DX coils used on electric heat units have left-hand
coilconnections.
3. Electric heat is available inthe reheat positiononly and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
*Left hand coil connections only.