Table3-- Electric Heater Data for Units with ECM (cont)
UNIT HP NOMINAL NUMBER
OF FLA LAT MCA
V/Ph/Hz ELEMENTS (F)
4OUH2OO
(at 2000 Cfm)
¾
208/1/60
240/1/60
277/1/60
77,7 102 97.1
208/3/60
3
4
5
6*
3
4
5*
6
3
4
5
240/3/60
50.1
64.6
79.0
93.5
56.8
73.5
90.1
48,8
63.3
84
89
94
99
89
96
102
89
96
62.7
80.7
99.8
116.8
71.0
91.8
112.7
61.0
79.1
TOTAL
MOCP CAPACITY
(kw)
70 9.0
90 12.0
100 15.0
125 18.0
80 12.0
100 16.0
125 20.0
70 12.0
80 16,0
100 20.0
40 9.0
60 12.0
80 15.0
80 18.0
45 12.0
70 16.0
90 20.0
90 24.0
25 12.0
35 16.0
40 20.0
40 24.0
460/_60
6
3
4
5
6
3
4
5
6
3
4
5
6
LEGEND
DX -- Direct Expansion
FLA -- Full Load Arnps
I.AT -- Leaving-Air Temperature at 70 F Entering-Air
Temperature
31.8
46.3
56.9
56.9
35.7
52.4
64.6
64.6
16.9
25.2
31.3
31.3
84
89
94
99
89
96
102
109
89
96
102
108
39.8
57.9
71,1
71.1
44,6
65.5
80.8
80.8
21.1
31.5
39.1
39.1
MCA -- Unit Minimum Circuit Ampacity
MOCP -- Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC -- Permanent Split Capacitor
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coils used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat positiononly and connec-
tions are on the rightside,
4. Face and bypass units are available with 3 heating elements
only.
*Left hand coil connections only.