Performance data (cont)
IMPORTANT
Unit 42BH standard motors are rated for a maximum ambient
air temperature of 104 F when fully loaded.
Since these are draw-through units,
it will be necessary to
calculate the air temperature leaving the coil for all heating
applications. If this temperature exceeds 104 F, consult Syra-
cuse to determine availability and price of special units.
Leaving Air Temp
MBtuh x 1000
= + Ent Air Temp
1.08 x Cfm
HEATING CAPACITY CURVES (cont)
24