EasyManua.ls Logo

Carrier 42BH Series - Nominal Cooling Capacities

Carrier 42BH Series
27 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42BH NOMINAL COOLING CAPACITIES
UNIT SIZE
42BH
NOMINAL CFM COIL ROWS EWT GPM
COOLING*
Total Capacity Sensible Capacity
(MBtuh) (MBtuh)
08 800
4
40 6.6 33.0 21.2
45 4.9 24.4 17.7
50 3.0 15.0 14.6
6
40 7.8 39.0 24.7
45 6.0 30.0 21.4
50 4.2 21.0 18.5
12 1200
4
40 10.4 52.0 31.0
45 7.9 39.5 26.0
50 5.2 26.0 22.0
6
40 12.6 63.0 37.5
45 9.8 49.0 32.5
50 7.0 35.0 27.0
16 1600
4
40 14.2 71.0 44.5
45 10.2 51.0 38.0
50 6.2 31.0 31.0
6
40 16.2 81.0 50.0
45 11.9 59.5 42.0
50 7.5 37.5 33.0
20 2000
4
40 18.8 94.0 58.0
45 13.4 67.0 48.0
50 8.6 43.0 39.0
6
40 21.0 105.0 63.5
45 16.0 80.0 52.2
50 11.0 55.0 42.0
30 3000
4
40 25.6 128.0 83.0
45 18.4 92.0 70.5
50 13.9 69.5 56.7
6
40 32.9 164.5 98.0
45 25.6 128.5 84.0
50 18.5 92.5 68.0
40 4000
4
40 36.4 182.0 116.5
45 28.0 140.0 100.0
50 19.2 96.0 80.0
6
40 44.4 222.0 134.0
45 34.9 174.5 112.5
50 25.6 128.0 92.5
EWT Entering Water Temperature
*Based on entering air temperature of 67 F wb, 80 F db and temperature rise of 10 degrees F.
NOTES:
1. All ratings at sea level.
2. Ratings in accordance with ARI.
9

Related product manuals