EasyManua.ls Logo

Carrier 42CA - Page 44

Carrier 42CA
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
44
Table 5 — Piping Components (cont)
LEGEND *Check all system component pressure ratings (coils, values,
pumps, etc.) with manufacturer and any applicable local or national
piping codes prior to specifying system pressure rating.
SYMBOL/SKETCH DESCRIPTION
C
V
FACTOR RATING*
STEAM
USE
1
/
2
3
/
4
PSI F
2-WAY MOTORIZED VALVE (150 PSI close off dif-
ferential pressure): Electric 2-position flow control
valve (open/closed). Normally closed body with man-
ual override lever. Installed in supply line to unit.
Application — All standard control and valve pack-
ages are based upon normally closed valves (valve
electrically powered open and closed by spring
return when electric power removed). Manual over-
ride lever allows valve to be placed in the open posi-
tion for secondary (unit) flushing, constant water flow
prior to start-up, etc. Manual override is automati-
cally disengaged when valve is electrically activated.
Consult factory for normally open valve applica-
tions.
4.9 10.3 300 240 NO
3-WAY MOTORIZED VALVE (25 PSI close off dif-
ferential pressure): Electric 2-position flow control
valve (closed to coil/open to bypass or open to coil/
closed to bypass). Normally closed with manual
override lever. Installed in supply line to unit.
Application — Same comments as 2-way motorized
valve except with manual override lever engaged the
valve is open to both ports and water flow will take
the path of least resistance through the valve pack-
age (not necessarily 100% through the coil).
4.0 4.0 300 200 N/A
3-WAY MOTORIZED VALVE (150 PSI close off dif-
ferential pressure): Electric 2-position flow control
valve (closed to coil/open to bypass or open to coil/
closed to bypass). Normally closed with manual
override lever. Installed in supply line to unit.
Application — Same comments as 2-way motorized
valve except with manual override lever engaged the
valve is open to both ports and water flow will take
the path of least resistance through the valve pack-
age (not necessarily 100% through the coil).
4.9 4.9 300 240 N/A
MODULATING VALVE (Optional)
(Non-Spring Return, Floating Point Actuator):
Modulating valves are designed to control the flow in
the circuit by making incremental adjustments to the
flow path within the valve.
Application — To control fluid flow in fan coil units.
On the 42DD commercial fan coil models, the factory
provided modulating valve has application restric-
tions. In these models, the valve packages are
located in the airstream, downstream of the coil. Due
to the ambient temperature limitations of the modu-
lating valves, the valves can only be used in the units
listed above with 2-pipe cooling only systems.
4.0 300 200
N/A
C
v
Coefficient of Velocity
DX Direct Expansion
ETO Engineering to Order

Related product manuals