EasyManua.ls Logo

Carrier 42HQG018 - DIP SWITCHES CONFIGURATION

Carrier 42HQG018
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86
42HQG024 + 38YL24 Heating mode
TEMPERATURE
(°C) DRY BULB AIR TEMPERATURE ENTERING
AIR ENTERING OUTDOOR COIL (°C)
INDOOR COIL
-15 -10 -7 -2 2 7 10 15 20
TH 3.76 4.43 4.86 5.65 6.36 7.32 7.76 8.42 8.84
15 THI 3.45 4.06 4.40 5.00 5.51 7.32 7.76 8.42 8.84
KW 1.72 1.81 1.87 1.99 2.11 2.29 2.35 2.47 2.54
TH 3.66 4.32 4.76 5.53 6.24 7.17 7.73 8.45 9.01
20 THI 3.37 3.97 4.31 4.88 5.41 7.17 7.73 8.45 9.01
KW 1.88 1.97 2.03 2.17 2.29 2.48 2.59 2.72 2.84
TH 3.55 4.22 4.64 5.39 6.13 7.04 7.65 8.48 9.27
25 THI 3.26 3.87 4.22 4.76 5.32 7.04 7.65 8.48 9.27
KW 2.05 2.15 2.23 2.36 2.49 2.70 2.83 2.99 3.18

Related product manuals